User Manual

Cod.Doc.2550041-REV02.doc
Pagina 45
Group 7
Network parameters
P7.01 Mains voltage minimum threshold (measured) 160 – 230Vac 195Vac
.02 Mains voltage maximum threshold (measured) 200 – 345Vac 260Vac
.03 Mains voltage time out of the limits 5 – 9999 sec 5 sec
.04 Mains voltage return time within the limits 5 – 9999 sec 10 sec
Group 8
Generator parameters
P8.01 Generator voltage minimum threshold (measured) 160 – 230Vac 195Vac
.02 Generator voltage maximum threshold (measured) 200 – 345Vac 260Vac
.03 Generator voltage delay out of the limits 5 – 9999 sec 5 sec
.04 Generator voltage time within the limits 5 – 9999 sec 20 sec
Alarms
Setup Description Range Default
0000=no 0001=yes
A1 Engine overtemperature 0000 / 0001 0001 = yes
A1.01 Stop without cooling 0000 / 0001 0001 = yes
A1.02 Stop with cooling 0000 / 0001 0000 = no
A1.03 Siren relay 0000 / 0001 0001 = yes
A1.04 Alarm relay (if enabled see P6.02) 0000 / 0001 0001 = yes
A1.05 Not used 0000 / 0001 0000 = no
A2 Oil low pressure 0000 / 0001 0001 = yes
A2.01 Stop without cooling 0000 / 0001 0001 = yes
A2.02 Stop with cooling 0000 / 0001 0000 = no
A2.03 Siren relay 0000 / 0001 0001 = yes
A2.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A2.05 Not used 0000 / 0001 0000 = no
A3 Avaria meccanica 0000 / 0001 0001 = yes
A3.01 Stop without cooling 0000 / 0001 0001 = yes
A3.02 Stop with cooling 0000 / 0001 0000 = no
A3.03 Siren relay 0000 / 0001 0001 = yes
A3.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A3.05 Not used 0000 / 0001 0000 = no
A4 500 rpm failure (strap breaking) 0000 / 0001 0001 = yes
A4.01 Stop without cooling 0000 / 0001 0000 = no
A4.02 Stop with cooling 0000 / 0001 0000 = no
A4.03 Siren relay 0000 / 0001 0001 = yes
A4.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A4.05 Not used 0000 / 0001 0000 = no
A5 Overspeed (maximum frequency) 0000 / 0001 0001 = yes
A5.01 Stop without cooling 0000 / 0001 0001 = yes
A5.02 Stop with cooling 0000 / 0001 0000 = no
A5.03 Siren relay 0000 / 0001 0001 = yes
A5.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A5.05 Not used 0000 / 0001 0000 = no
A6 Minimum frequency (fixed delay 5sec) 0000 / 0001 0001 = yes
A6.01 Stop without cooling 0000 / 0001 0000 = no
A6.02 Stop with cooling 0000 / 0001 0001 = yes
A6.03 Siren relay 0000 / 0001 0001 = yes
A6.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A6.05 Not used 0000 / 0001 0000 = no
A7 Generator minimum voltage 0000 / 0001 0001 = yes
A7.01 Stop without cooling 0000 / 0001 0001 = yes
A7.02 Stop with cooling 0000 / 0001 0000 = no
A7.03 Siren relay 0000 / 0001 0001 = yes
A7.04 Alarm relay (if enabled) 0000 / 0001 0001 = yes
A7.05 Not used 0000 / 0001 0000 = no