ELECTRICAL PANEL AT206 / AT206B USER MANUAL Cod.Doc.2550041-REV02.
INDEX: 1 - General ...........................................................................................................................................................................................................................27 1.1 - Introduction ...............................................................................................................................................................................................................27 1.2 - General warning.....................
1 - GENERAL The Instruction for Use are integral part of the machine and must accompany it for all its useful life until its demolition. For every operation one must always apply to what is prescribed in the Instructions. Follow scrupolously all indication reported in the Instructions Prevent from making use of the machine operators not knowing the prescription based on the Instructions Keep complete and legible Instructions in a place accessible to operators.
- This electric panel has only to be used for the purpose for which it was specifically designed. Any other use shall be considered improper and, therefore, dangerous. - Our products are made in conformity with current safety standards so it is recommended to use all these devices and take care that their use causes no injury or damage. - All operations concerning the installation of the control panel should be carried out by skilled personnel in conformity with present regulations.
1.4 - Important tips User tips on safety: N.B. The information contained in this manual may be changed without notice. Any damage caused in relation to the use of these instructions shall not be considered since they are only guidelines. We remind you that failure to observe the instructions we give could cause injury or damage. It is anyhow understood that current local regulations and/or laws must be observed. 1.5 - Cautions Hazardous situations - safety for persons and objects.
1.9 - Transporting Transportation of the electric panel must be done so as not to jeopardize its structure. On receiving the panel, inspect it for any damage suffered in transit and that the data given on the rating plate correspond to what you requested. Any damage must be reported in writing to the carrier directly when the goods are received. Compensation for damage will be paid in accordance with current legislation on carriage.
2- AT206 PANEL DESCRIPTION This product permit to control all the functions about a generator • • • • Engine command and protection module for diesel or gasoline generators Measurement system for main electric values Automatic control module for two different supply sources (Automatic Mains Failure) Automatic changeover switch from two different supply sources (Automatic Transfer Switch) It’s builded to monitor monophase, triphase or triphase with neutral systems in alternate current; it permit to transfe
2.2 - Product external and internal view with description Control board F1 = F4A F2 = F2A F3 = F2A Buzzer “B” for acoustic alarm “IMP” switch to supply 230Vac for auxiliary output. (OPTIONAL) Predisposition for magnetothermic switch or earth failure relay.
2.3 - Panel wall mounting instructions WARNING: THE INSTALLATION OF THE PANEL MUST BE MADE ONLY BY SKILLED PEOPLE The panel must be fixed on the wall by two fixing hook in equipment . For air flow reasons, it is necessary that around the panel there is a free space of about 10cm for all the perimeter 3 - FIRST STARTING OF THE PRODUCT, USE AND DESCRIPTION 3.
3.2 - AT206 panel; LED indication decription 4 digit multifunction display to show measurement, function and alarms status Type of measurement showed by the display If flashing, it indicate that the engine is running and the alarms are not enable. If on, it indicate that the engine is running and the alarms are enable. If on, it indicates that the voltage measured is about the mains If on, it indicates that the board is in MANUAL (Par. 3.
3.4 - AT206 panel; function description BOARD IN RESET The generator can’t work. If the mains is ok, the mains contactor is closed. If the generator is running, when you change to this function mode the engine is stopped immediatly and the eventual alarms are resetted. The alarm can’t be resetted if the cause of alarm still remain.
4 - AT206 CONNECTION AND ELECTRICAL DRAWINGS 4.1 - Power connection 4.1.1 - Triphase connection 400Vac 3P+N Generator contactor TG1. Terminals sequence: T1-T2-T3-T4 Mains contactor TR1. Terminals sequence: T1-T2-T3-T4 Load connection X0.
4.1.2 - Triphase connection 230Vac 3P+N Generator contactor TG1. Terminals sequence: T1-T2-T3-T4 Mains contactor TR1. Terminals sequence: T1-T2-T3-T4 Load connection X0. Terminals sequence: U-V-W-N Phase 1 load: U It pass through TA before connection to load terminal U Generator neutral: T4 Generator phase 3: T3 Phase 2 load: V Generator phase 2: T2 Phase 3 load: W Generator phase 1: T1 Neutral load: N Warning!! Move blue wire n.
4.1.3 - Monophase connection 230Vac Generator contactor TG1. Terminals sequence: T1-T2-T3-T4 Load connection X0. Terminals sequence: U-V-W-N Mains contactor TR1. Terminals sequence: T1-T2-T3-T4 Generator neutral: to use maximum contactor power, poles T3 and T4 must be connected togheter; T3+T4=Neutral. By this connection the max current of the contactor is Ith x 1,6 Load phase: to use maximum terminals power, poles U and V must be connected togheter; U+V=Phase.
4.2 - AT206 panel electrical drawing Cod.Doc.2550041-REV02.
4.3 - AT206B panel electrical drawing Cod.Doc.2550041-REV02.
4.4 - Diesel engine auxiliary connection Cod.Doc.2550041-REV02.
4.5 - Gasoline engine auxiliary connection Cod.Doc.2550041-REV02.
Cable connection and fixing power on contactor’s terminals and output terminals, must be in accordance to following data Minimum and maximum terminals fixing power .Warning!!! During Minimum and maximum section Contactor (check the type the power cables connection, don’t move the auxiliary wires from of the cables connected without installed in the panel) the contactor terminals and check if they are properly fixed terminals togheter with power cables in the terminals.
5.4 - Advanced menu parameters Setup Group 1 P1.01 .02 .03 Group 2 P2.01 Description Panel nominal data Nominal frequence Current Trasformer ratio (CT 100/5 = 20) System (220V monophase, 220V triphase, 380V triphase) Engine start-up 500 rpm signal from alternator or gen. (started engine) Range 50Hz= 0 60Hz=1 1…2000 0=220M 1=220T 2=380T Default 0 20 0 .02 .03 .04 .05 .06 .07 .08 .
Group 7 P7.01 .02 .03 .04 Network parameters Mains voltage minimum threshold (measured) Mains voltage maximum threshold (measured) Mains voltage time out of the limits Mains voltage return time within the limits 160 – 230Vac 200 – 345Vac 5 – 9999 sec 5 – 9999 sec 195Vac 260Vac 5 sec 10 sec Group 8 P8.01 .02 .03 .
A8 A8.01 A8.02 A8.03 A8.04 A8.05 Generator maximum voltage Stop without cooling Stop with cooling Siren relay Alarm relay (if enabled) Not used 0000 / 0001 0000 / 0001 0000 / 0001 0000 / 0001 0000 / 0001 0000 / 0001 0001 = yes 0000 = no 0001 = yes 0001 = yes 0001 = yes 0000 = no A9 A9.01 A9.02 A9.03 A9.04 A9.
6 - GENERAL SALES CONDITIONS AND WARRANTY PRICES The prices are those specifically valid of the ruling price list, VAT excluded. Furthermore, they do not cover the costs of packing, carriage, delivery, custom duties and/or any other charges, unless stated otherwise. Except when agreed with TECNOELETTRA in writing, the ruling prices shall be applied to all deliveries beginning from January 1.
Cod.Doc.2550041-REV02.