Group 7 
Network parameters
P7.01  Mains voltage minimum threshold (measured)  160 – 230Vac  195Vac 
 .02  Mains voltage maximum threshold (measured)  200 – 345Vac  260Vac 
 .03  Mains voltage time out of the limits  5 – 9999 sec  5 sec 
 .04  Mains voltage return time within the limits  5 – 9999 sec  10 sec 
Group 8 
Generator parameters
P8.01  Generator voltage minimum threshold (measured)  160 – 230Vac  195Vac 
 .02  Generator voltage maximum threshold (measured)  200 – 345Vac  260Vac 
 .03  Generator voltage delay out of the limits  5 – 9999 sec  5 sec 
 .04  Generator voltage time within the limits  5 – 9999 sec  20 sec 
Alarms  
Setup Description  Range Default 
   0000=no 0001=yes   
A1  Engine overtemperature  0000 / 0001  0001 = yes 
A1.01  Stop without cooling  0000 / 0001  0001 = yes 
A1.02  Stop with cooling  0000 / 0001  0000 = no 
A1.03 Siren relay  0000 / 0001  0001 = yes 
A1.04  Alarm relay (if enabled see P6.02)  0000 / 0001  0001 = yes 
A1.05 Not used  0000 / 0001  0000 = no 
A2  Oil low pressure  0000 / 0001  0001 = yes 
A2.01  Stop without cooling  0000 / 0001  0001 = yes 
A2.02  Stop with cooling  0000 / 0001  0000 = no 
A2.03 Siren relay  0000 / 0001  0001 = yes 
A2.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A2.05 Not used  0000 / 0001  0000 = no 
A3  Avaria meccanica  0000 / 0001  0001 = yes 
A3.01  Stop without cooling  0000 / 0001  0001 = yes 
A3.02  Stop with cooling  0000 / 0001  0000 = no 
A3.03 Siren relay  0000 / 0001  0001 = yes 
A3.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A3.05 Not used  0000 / 0001  0000 = no 
A4  500 rpm failure (strap breaking)  0000 / 0001  0001 = yes 
A4.01  Stop without cooling  0000 / 0001  0000 = no 
A4.02  Stop with cooling  0000 / 0001  0000 = no 
A4.03 Siren relay  0000 / 0001  0001 = yes 
A4.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A4.05 Not used  0000 / 0001  0000 = no 
A5  Overspeed (maximum frequency)  0000 / 0001  0001 = yes 
A5.01  Stop without cooling  0000 / 0001  0001 = yes 
A5.02  Stop with cooling  0000 / 0001  0000 = no 
A5.03 Siren relay  0000 / 0001  0001 = yes 
A5.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A5.05 Not used  0000 / 0001  0000 = no 
A6  Minimum frequency (fixed delay 5sec)  0000 / 0001  0001 = yes 
A6.01  Stop without cooling  0000 / 0001  0000 = no 
A6.02  Stop with cooling  0000 / 0001  0001 = yes 
A6.03 Siren relay  0000 / 0001  0001 = yes 
A6.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A6.05 Not used  0000 / 0001  0000 = no 
A7  Generator minimum voltage  0000 / 0001  0001 = yes 
A7.01  Stop without cooling  0000 / 0001  0001 = yes 
A7.02  Stop with cooling  0000 / 0001  0000 = no 
A7.03 Siren relay  0000 / 0001  0001 = yes 
A7.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A7.05 Not used  0000 / 0001  0000 = no 