Pramac-2-Wire-Auto-Start-Controller
Cod.Doc.2550041-REV02.doc 
Pagina 46 
A8  Generator maximum voltage  0000 / 0001  0001 = yes 
A8.01  Stop without cooling  0000 / 0001  0000 = no 
A8.02  Stop with cooling  0000 / 0001  0001 = yes 
A8.03 Siren relay  0000 / 0001  0001 = yes 
A8.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A8.05 Not used  0000 / 0001  0000 = no 
A9  Fuel  0000 / 0001  0001 = yes 
A9.01  Stop without cooling  0000 / 0001  0000 = no 
A9.02  Stop with cooling  0000 / 0001  0000 = no 
A9.03 Siren relay  0000 / 0001  0001 = yes 
A9.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A9.05 Not used  0000 / 0001  0000 = no 
A10  Maximum current  0000 / 0001  0001 = yes 
A10.01  Stop without cooling  0000 / 0001  0000 = no 
A10.02  Stop with cooling  0000 / 0001  0001 = yes 
A10.03 Siren relay  0000 / 0001  0001 = yes 
A10.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A10.05 Not used  0000 / 0001  0000 = no 
A11  Battery minimum voltage  0000 / 0001  0001 = yes 
A11.01  Stop without cooling  0000 / 0001  0000 = no 
A11.02  Stop with cooling  0000 / 0001  0000 = no 
A11.03 Siren relay  0000 / 0001  0001 = yes 
A11.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A11.05 Not used  0000 / 0001  0000 = no 
A12  Battery maximum voltage  0000 / 0001  0001 = yes 
A12.01  Stop without cooling  0000 / 0001  0000 = no 
A12.02  Stop with cooling  0000 / 0001  0001 = yes 
A12.03 Siren relay  0000 / 0001  0001 = yes 
A12.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A12.05 Not used  0000 / 0001  0000 = no 
A13  Starting failure  0000 / 0001  0001 = yes 
A13.01  Stop without cooling (not influential, always as set to “no”)  0000 / 0001  0000 = no 
A13.02  Stop with cooling (not influential, always as set to “no”)  0000 / 0001  0000 = no 
A13.03 Siren relay  0000 / 0001  0001 = yes 
A13.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
A13.05 Not used  0000 / 0001  0000 = no 
E1  Remote stop  0000 / 0001  0001 = yes 
E1.01  Stop without cooling (not influential, always as set to “yes”)  0000 / 0001  0001 = yes 
E1.02  Stop with cooling (not influential, always as set to “no”)  0000 / 0001  0000 = no 
E1.03 Siren relay  0000 / 0001  0001 = yes 
E1.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
E1.05 Not used  0000 / 0001  0000 = no 
E2  Emergency stop (not influential, always as set to “yes”)  0000 / 0001  0001 = yes 
E2.01  Stop without cooling (not influential, always as set to “yes”)  0000 / 0001  0001 = yes 
E2.02  Stop with cooling (not influential, always as set to “no”)  0000 / 0001  0000 = no 
E2.03 Siren relay  0000 / 0001  0001 = yes 
E2.04  Alarm relay (if enabled)  0000 / 0001  0001 = yes 
E2.05 Not used  0000 / 0001  0000 = no 