2.3 - Panel wall mounting instructions 
 WARNING: THE INSTALLATION OF THE PANEL MUST BE MADE ONLY BY SKILLED PEOPLE 
3 - FIRST STARTING OF THE PRODUCT, USE AND DESCRIPTION 
3.1 - Operation to do during the first starting of the AT206 panel 
When you supply for the first time the panel, the display shows “U11” flashing, to remember you the time programmation (User menu, parameter U11). 
Press RESET button to stop this flashing and set the board in RESET position. 
The non observance of the indications given about the first starting of the product, can cause faulty situations on the same product 
Before the first starting of the panel, check that the indications on the “Identification data plate” (par. 2.1.1) are in accordance with the 
characteristics of the present electrical system. 
The programmation of time is needed 
3.1.1 - How programming the time on the panel 
To program the time, follow the procedure descripted below: 
-  Press RESET button 
-  With the board in RESET position, press TEST button for 5 seconds until the display shows “Set”; after that the display shows the first code of the 
parameter “U.01 – Automatic test interval time”. To see all the parameters, please check the following table 
-  By continously pressing of MEAS button, reach parameter “U.11” showed on the display. This parameter is about the actual time. 
-  Press TEST button to see the value stored now. 
-  Press START button to increase the value of the hour or press STOP button to increase the value of the minutes 
-  When the time is correct, press RESET button to save it and press AUT button to return on the parameter code (the display shows U.11) 
-  Press AUT button than RESET button to exit from menu and return to the normal function mode. 
Setup Description  Range  Default 
Group 1  Test   
U.01  Automatic test interval time  1 – 30days  3 days 
U.02  Test duration  1 – 30 min  10 min 
U.03  Test start time  00:00 – 23:59  10:00 
U.04  Test with load  0=with load 1=without load  1 
Group2 Various   
U.08  Siren relay closing time  0 – 60 sec  20 sec 
U.09  Engine departure delay from EJP/T start  0 – 99 min  25 min 
U.10  Switching delay for EJP/T(1 wire)  0 – 30 min  5 min 
Group3 Clock setting   
U.11  Time  00:00 – 23:59  11:11 
For air flow reasons, it is necessary that 
around the panel there is a free space of 
about 10cm for all the perimeter 
The panel must be fixed on the wall by 
two fixing hook in equipment 
. 