Product Card

S6500 (24L) 230V 50HZ #CONN #DPP
THE COMPLETE DIESEL PACKAGE
Showing the excellence of Pramac's professional equipment, this generator offers a
robust package with a modern and economical Diesel engine. Perfect for intensive
use, it's equiped with a control panel which allows to integrate many accessories and
options for better confort and for optimal command.
Main Features
Frequency Hz 50
Voltage V 230
Power factor cos ϕ 0.9
Phase and connection 1
Power Rating
Standby power LTP kVA 5.9
Standby power LTP kW 5.3
Continuous power COP kVA 4.8
Continuous power COP kW 4.4
Ratings definition (According to standard ISO8528 1:2005)
COP - Continuous Power: It is defined as being the maximum power which a generating set is capable of
delivering continuously for an unlimited number of hours, with the maintenance intervals and procedures
being carried out as prescribed by the manufacturers.
LTP - Limited-Time running Power: It is defined as the maximum power available, under the agreed
operating conditions, for which the generating set is capable of delivering for up to 500 h of operation per
year (whose no more than 300 for continuative use) with the maintenance intervals and procedures being
carried out as prescribed by the manufacturers. No overload capability is available.