User Manual

39
UNIVERSAL TRANSMITTER
PReasy 4116
Input for RTD, TC, Ohm, potentiometer, mA and V
2-wire supply > 16 V
FM-approved for installation in Div. 2
Output for current, voltage and 2 relays
Universal AC or DC supply
Advanced features
Programmable via detachable display front (4501), process calibration, signal
and relay simulation, password protection, error diagnostics and selection of
help text in several languages.
Application
Linearised, electronic temperature measurement with RTD or TC sensor.
Conversion of linear resistance variation to a standard analogue current /
voltage signal, i.e. from solenoids and butterfly valves or linear movements
with attached potentio meter.
Power supply and signal isolator for 2-wire transmitters.
Process control with 2 pairs of potential-free relay contacts and analogue
output.
Galvanic separation of analogue signals and measurement of floating signals.
The 4116 is designed according to strict safety requirements and is thus suit-
able for application in SIL 2 installations.
Technical characteristics
When 4116 is used in combination with the 4501 display / programming front,
all operational parameters can be modified to suit any application. As the
4116 is designed with electronic hardware switches, it is not necessary to
open the device for setting of DIP switches.
A green / red front LED indicates normal operation and malfunction. A yellow
LED is ON for each active output relay.
Continuous check of vital stored data for safety reasons.
4-port 2.3 kVAC galvanic isolation.