AutoPar®, Bad Boy®, PRG Series 400®, Mbox Extreme®, V676®, Virtuoso®, Virtuoso® DX, and Virtuoso® DX2, are trademarks of Production Resource Group, LLC, registered in the U.S. and other countries. All other brand names which may be mentioned in this manual are trademarks or registered trademarks of their respective companies. This manual is for informational use only and is subject to change without notice. Please check www.prg.com for the latest version.
INTRODUCTION About This Guide This guide provides necessary information regarding product safety, installation, and operation for the following PRG equipment: + PRG Series 400® 400 Amp Disconnect (20.9680.0200) Familiarizing yourself with this information will help you get the most out of your PRG product. WARNING: It is important to read ALL accompanying safety and installation instructions to avoid damage to the product and potential injury to yourself or others.
Customer Service For technical assistance, contact the PRG International Service Center or contact your nearest PRG office. Contact information for all PRG office locations can be found on our website at: www.prg.com/about-us/locations/ PRG Dallas (International Service) 8617 Ambassador Row, Suite 120 Dallas, Texas 75247 USA Phone: 214.630.1963 Fax: 214.630.5867 Service Fax: 214.638.2125 Service Email: orders@prg.com For additional resources and documentation, please visit our website at: www.prg.
OVERVIEW Description The PRG Series 400® 400 Amp Disconnect is a safety device containing a three-phase, 400 Amp circuit breaker serving as a Main Breaker for high current AC power distribution systems. A Disconnect unit is required when 5-wire, 4/0 AWG feeder cables greater than 10 feet in length are connected from a house service greater than 400 Amps per phase to a portable power distribution system.
Controls and Indicators The S400 Disconnect contains the following connections and LED indicators. Voltmeters - measures phase voltages to ensure supply voltage is correct. Voltage input to the Cam-Loks is measured before the breakers and will show the input voltage even when the Main Breaker is off. INPUT VOLTAGES 600A MAX Voltmeter Rocker Switch - allows connection of the meters between the three phases (Ø-Ø) or between each phase and neutral (Ø-N).
120/208V 3Ø OUTPUTS 400A PER Ø MAX NEUT YØ GND NEUT GND XØ NEUT ZØ Power Output Connectors Two sets of six Cam-Lok connectors for power output to power distribution systems. YØ S-400 400 AMP DISCONNECT NEUT XØ ZØ INPUT CONNECTIONS MUST BE MADE IN THE FOLLOWING ORDER: 1) CONNECT GROUND 2) CONNECT NEUTRAL 3) CONNECT PHASES DISCONNECT IN REVERSE ORDER 120/208V 3Ø INPUTS 400A PER Ø MAX XØ YØ ZØ Neon Phase Lamps Indicate presence of AC voltage for each of three phases.
INSTALLATION Installing S400 Disconnect The S400 Disconnect is installed between the house service and a portable power distribution system, such as the PRG Series 400 Power and Data Distribution System. It may also be used to protect a dimmer installation. CAUTION: Before installing, refer to "Proper Use and Operation" on page 3. WARNING: Ensure house service main breaker and S400 Disconnect breaker are OFF before connecting mains power cables. Ground should always be connected first. To install: Step 1.
Step 5. Ensure that Main Breaker is switched OFF (Figure 4). Step 6. At INPUTS, connect input power cable Cam-Loks in the following order: 1) Ground, 2) Neutral 3) X Phase, 4) Y Phase, and 5) Z Phase.
Set the Inrush Current Limit: Some loads, such as incandescent lamps or electric motors, can draw a large surge of current through the Main Breaker when they are quickly energized with voltage. When the Inrush Current Limit of the Main Breaker is exceeded, the Breaker will trip within a half cycle of the AC line. It is important that the Inrush Current Limit be properly adjusted so that these normal, but large surges do not cause nuisance tripping of the Main Breaker.
Power Up Sequence Use the following procedure to power up unit: Step 1. At house service main breaker, turn power ON. Step 2. At rear of Disconnect, verify all phase indicators are lit (Figure 6). NEUT DISCONNECT XØ ZØ INPUT CONNECTIONS MUST BE MADE IN THE FOLLOWING ORDER: 1) CONNECT GROUND 2) CONNECT NEUTRAL 3) CONNECT PHASES DISCONNECT IN REVERSE ORDER 120/208V 3Ø INPUTS 400A PERØ MAX XØ YØ ZØ Phase Indicators NEUT GND YØ NEUT XØ ZØ Figure 6: Phase Indicators Location Step 3.
MAINTENANCE Cleaning/Replacing Rack Air Filters The air filters, located in the interior rack assembly, will require periodic cleaning. The frequency will depend on the amount of use and/or exposure to dusty environments. Parts: 40.7155.0120.0 FILTER, FAN 120MM, MESH ALUMINUM Tools: #2 slotted screwdriver WARNING: Remove power from rack before performing any maintenance procedures. To clean/replace rack air filters: Step 1. Disconnect ALL power from rack. Step 2.
SPECIFICATIONS Technical Specifications RATINGS and AMPACITY Voltage Rating: 120/208V 3-phase wye with Neutral and Ground Line Frequency: 50 - 60 Hz Current Rating, Phases: 400 Amps per phase continuous Current Rating, Neutral: 600 Amps continuous Current Rating, Ground: 400 Amps Fault Current Interrupting Capacity: 42,000 Amps Fault Current Interrupt Time: Circuit clears in less than one line cycle MAIN BREAKER Type: Thermal-Magnetic, Square D Model LAL36400 Number of Poles: 3 Voltage Rat
COMPLIANCE UL Standard 1640 Canadian Standard CAN/CSA STD C22.2 No.
PRG Series 400® 400 Amp Disconnect User Manual Version as of: October 25, 2010 PRG part number: 02.9680.