WIRE CONNECTIONS TO AIR WIND TURBINE
Secure connecons using "split bolt" or solder connectors. Use color coded
wires - red for baery posive, black for baery negave, and green for
earth ground. Size wiring based on wiring tables provided. Insulate connec-
ons with heat shrink tubing or good quality electrical tape. Leave su-
cient service loop in the wires to accommodate removal of the turbine
from the tower.
FINAL CONNECTIONS
Follow system wiring diagram and run wires to disconnect switch, fuse or
circuit breaker and ammeter.
Before making baery connecons, make sure circuit breakers and stop
switch (highly recommended) are in the OFF posion. Aach wires to
baery; red to posive baery terminal and black to negave baery
terminal.
Complete baery connecons and switch ON circuit breakers and stop
switch. When power is switched on, the turbine LED will illuminate for two
seconds, go o for two seconds and illuminate for four seconds. This indi-
cates the internal
controller is funconing. The LED remains illuminated if the turbine is
charging the baery.
The installaon is now complete.
WARNING: Do not connect wires to baeries unl all electrical
connecons are completed.
WARNING: Reversed wire connecons will damage the AIR wind
turbine’s electronics. The polarity of the AIR wind turbine’s wires may be
checked by connecng a voltmeter to the wires and spinning the rotor
by hand.
2005 NEC Secon
Arcle 250.52, item 5
Arcle 250.53, item A
Arcle 250.53, item G
Arcle 250.64
Arcle 250.66, item A
Arcle 270.70
Topic
Tower Grounding
Tower Grounding
Grounding Electrode Installaon
Grounding Conductor Roung and Placement
Grounding Conductor Size
Bonding of Grounding Conductor
Cable Clamp
Tower
Grounding Conductor
6 AWG minimum.
Must be secured and
1 .
(0.3 m)
Grounding Wire Clamp
Grounding Rod
Exisng Grade
8 .
(2.44m)
Foundaon