UIDELINES FOR INSTALLATION OF PRO-FLEX
®
(
CSST) FLEXIBLE GAS PIPING IN OUTDOOR
APPLICATIONS
PRO-FLEX
®
tubing and fittings meet all performance requirements for outdoor applications and comply with
A
NSI/AGA-LC1 standards.
I
n outdoor applications, the external yellow jacketing on
P
RO-FLEX
®
s
hould not be removed. All exposed tubing on
the outside of a structure or located between the ground and a 6 ft height must be protected in a sealed conduit or
w
eather-tight chase which is routed and secured to avoid mechanical damage.
When buried underground or encased in cement (slabs, foundations, etc.) the tubing must be routed within a plastic
watertight conduit. This nonmetallic conduit is to have an inside diameter 1/2 inch larger than the
PRO-FLEX
®
tubes
outer diameter. Exposed conduit ends must be sealed to prevent entry of water and debris. Local code authority will
always take precedence. Therefore make sure you check with your local building authority or code authority having
jurisdiction.
Gas Meter Connections:
Gas meters are generally supported by the building structure or by framework brackets independent of the structure.
Do not use
PRO-FLEX
®
CSST as a direct connection to any meter which must be supported by the piping. On
structure supported meters, accepted practice is to connect the meter outlet to a termination flange mounted on the
exterior wall or to penetrate the exterior wall with a steel pipe and provide a rigid attachment for the meter and
PRO-FLEX
®
tubing within the building.