Installation Instructions
CLEARANCE HOLES & NOTCHING
a. Bored Holes - In locations where CSST is installed through bored
holes in joists, rafters, or wood members, holes shall be bored so
that the edge of the hole is not less than 2 inc. (50.8 mm) from the
nearest edge of the wood member. Where this distance cannot be
maintained at any point, the CSST shall be protected by a listed
striker plate of the appropriate length and width installed in accor-
dance with the manufacturers installation instructions. The diame-
ter of the bored holes shall be a minimum of 1/2 in. (12.7 mm)
larger than the outside diameter of the tubing.
b. The size of the hole drilled through top plates, top frame members,
and sole plates, to allow the vertical passage of the tubing, shall
not exceed 1/2 of the width of the member. The hole should be
bored through the center of the member. (See figure 4-1.)
c. Where soles or plates are cut for tubing, the width of the cut shall
be 1/2 in. (12.7 mm) larger than the outside diameter of the tubing
but not greater than 2 in. (50.8 mm), and the tubing must be
protected with a listed striker plate of the appropriate length and
width installed in accordance with the manufacturers installation
instructions. (See figure 4-1.)
d. Where a hole is to be bored in a joist, the hole should be located
at the centerline, otherwise no closer than 2 in. (50.8 mm) from the
nearest edge of the joist, and the hole diameter shall not exceed
1/3 the depth of the joist.
(See figure 4-2.)
e. Where holes are to be bored in non-bearing vertical members of
the wall framing, the siz
e of such holes shall not be larger than 60
percent of the width of the member. (See figure 4-3.)
f.
Where holes are to be bored in bearing vertical members of the
wall framing, the size of such holes shall not be larger than 40 per-
cent of the width of the member. Holes up to 60 percent of the
member’s width are permitted if the members are doubled. No
more than two successive double bored members are permitted.
(See figure 4-4.)
g. Installing CSST in notches cut in either the top or bottom of joists
are prohibited.
The size and depth of installation clearance holes or notches for
routing the tubing through wall studs and joists shall comply with the
requirements of the local building code.
CSST THROUGH METAL FRAMING
a. When CSST passes through metal members, it shall be installed
and protected in accordance as follows:
b. When using Pro-Flex
®
Flexible Gas Piping (CSST) thru Metal
Enclosures the CSST tubing must be protected by grommets,
bushing or armor (Floppy-Flex
™
), PVC tape, shrink sleeve material
or a minimum of four (4) wraps of #10 Mil Duct-Tape. This is to
ensure that no physical contact will be made between the metal
and the CSST tubing that would cause mechanical wear.
DRILLING:
Drilling holes should be made approx. 1/2” greater than the outside diameter of
the CSST Tubing.
20
FIGURE 4-2 - Holes in Wood Joints
FIGURE 4-1
Holes and Cuts in Top and Sole Plates
FIGURE 4-4
Holes in Bearing Walls
Recommended Installation for
Clearance Holes for Routing CSST
T
ubing Size Drill Hole Size
3/8" 1-1/8"
1/2" 1-3/8"
3/4" 1-1/2"
1 1-3/4"
1
1
/4" 2-1/4"
No more than two successive
double board studs permitted
FIGURE 4-3
Holes in Non-Bearing Walls
248008 17498_TF_TrainingG.indd 24248008 17498_TF_TrainingG.indd 24 6/12/13 12:16 PM6/12/13 12:16 PM