Minitrend® GR GR Series Advanced Graphic Recorders Specifications 43-TV-03-17, May 2015 Crystal Clear Display • 5.
® Minitrend GR Recorder Function • • The Minitrend GR uses a digital colour TFT LCD Honeywell’s Minitrend GR recorder provides flexible screen to provide easy to read displays with wide electronic data acquisition and recording in a high viewing angles for the best all around data viewing. functionality DIN standard 144mm format recorder.
® Minitrend GR 3 Features Display • 5.7” High Resolution Colour Active TFT with more than 256,000 colours makes it easy to interpret process data and take action with the intuitive bar charts, digital values, trends or customised displays. A screen saver function can be set from 1 to 720 minutes to extend the life of the backlight. • Data Storage Internal Data Storage - 256MB to 3.7GB of expandable internal non-volatile flash memory is available for data storage and chart history.
® Minitrend GR 4 Modbus Master/Slave Concurrent Batch Mode (option) The recorder can communicate with up to 32 slave Batch enhances the management of data collected in devices on both RS485 and/or Ethernet at a maximum non-continuous process, known as batch processing, poll rate of 1 second (slowest 1 hour), with each slave up used in thermal treatment, sterilisation, and food to 8 “transactions” can be performed where a transaction processing and chemical reactions.
® Minitrend GR Standard features • CE Mark - Conformity with 2006/95/EC, Low Voltage Directive and 2004/108/EC EMC Directive. • Common Relay Output - A separate relay alarm output at the rear of the unit can be set up as an alarm output.
® Minitrend GR Options – Hardware • board, are available to count signals up to 25 kHz (max. 2 cards). Analogue Output - 2 or 4 outputs available per card. Output type: 0-20mA or 4-20mA. Nema 4X / IP66 - Nema 4X / IP66 protection available as an option. • Portable Recorders - Portable cases available as an accessory item. • Pulse Counting - Up to four counting inputs per SPCO 240V, 8 Digital I/O or 16 Digital I/O can be configured to activate up to 16 outputs.
® Minitrend GR 7 Firmware Credit System The credits system is a flexible way of adding to the recorder features without having to upgrade the firmware. Simply purchase a number of credits to cover your current and possible future requirements and the recorder will be delivered with the credits loaded. Credits can be applied as desired to the Firmware functions until the total number of credits purchased has been used up.
® Minitrend GR 8 Firmware option Credit value Description Batch/Groups 5 The Batch function allows the user to segment portions of data for further analysis. The Batch function manages sections of data. Concurrent batches are now associated with a group of pens. The pens with in each group will belong to the batch that is controlled by that group. Batches can be controlled through the event system and batch markers are setup by the user and are used to identify and analyse batches of data.
® Minitrend GR 9 The TrendManager Pro Software Suite Enhancements The TrendManager Pro Software Suite complements the Communications Server capabilities of the “GR Series” recorders by providing the This is supplied with TrendServer Pro. It manages real-time benefits of viewing, configuration, network communications, communications, distributed access to the stored data, time database management, data analysis and report generation synchronisation over RS-485 and Ethernet networks.
® Minitrend GR 10 Minimum System requirements for TrendViewer:· Minimum System requirements for TrendServer Pro, TrendManager Pro and GR Series Screen Designer: Supports: Microsoft Windows™ Windows 7 (32 and 64 bit – Professional, Enterprise and Ultimate Edition), Windows 2008, Windows 2008 Server, Windows 2012 Server. Supports: Microsoft Windows™ Windows 7 (32 and 64 bit – Professional, Enterprise and Ultimate Edition), Windows 2008, Windows 2008 Server, Windows 2012 Server.
® Minitrend GR 11 Specification Design Attributes Digital indicators and Display Display size and Type: 5.7” diagonal, Digital Colour LCD (TFT) with Touch Screen Industrial grade with brightness adjustment and wide viewing angle Resolution: VGA (640 x 480 pixels). Screen Saver: Set in minutes from 1 to 720, can be set to dim the screen or to switch off. Brightness adjustment: Adjustable between 10 and 100%, default set to 80% brightness.
® Minitrend GR 12 Specification Design Attributes Common Relay Output (SPNC) NC common alarm relay: Two contacts, normally open when the recorder is powered (no active alarms). Rating 24V, 1 Amp. Password Protection Multiple Administrator control of password setup and management with four levels of password protection for – Engineer, Supervisor, Technician, and Operator. Up to 50 different users are avail-able. Password protection restricts user entry to the recorder set up and specific screens.
® Minitrend GR 13 Specification Design Attributes Cold Junction Compensation Internal compensation with the ability to manually adjust values, External Input for compensation, External CJC value specified Input Resolution 0.0015% (16 Bit ADC) Input Impedance Current loop resistance: 10 ohms, use ±0.1% external resistor. Volts >1MΩ, all other 10MΩ Source Impedance T/C and RTD: 100 ohms per lead maximum. (A single point cal on Slot A will improve accuracy for a lead resistance above 10 ohms).
® Minitrend GR 14 Input Range Performance and Accuracy Range Accuracy Temp. Stability +/- Millivolts DC -5 to 5, -10 to 10, -25 to 25, -50 to 50, -100 to 100, -250 to 250, -500 to 500, -1000 to 1000 +/- 0.2% F.S. +/- 0.1% F.S. +/- 0.1% F.S. +/- 0.1% F.S. 0.01%/ °C 0.01%/ °C 0.01%/ °C 0.01%/ °C >10M ohms >10M ohms >10M ohms >10M ohms Volts DC -0.3 to 0.3, -0.6 to 0.6, -1.5 to 1.5, -3 to 3, -6 to 6, -12 to 12, -25 to 25, -50 to 50 0.01%/ °C 0.01%/ °C 0.
® Minitrend GR 15 Range Input Actuation (T/Cs) Ref. Accuracy Temp. Stability +/- Field Cal Deg°F Field Cal Deg °C °F °C +/- °F +/- °C N* (Nicrosil Nisil) -328 to 212 212 to 2372 -200 to 100 100 to 1300 5.8 2.0 3.2 1.1 0.01%/ °C 5.8 1.0 3.2 0.56 Chromel/Copel* -58 to 1112 -50 to 600 1.1 0.6 0.01%/ °C 0.54 0.3 P* (Platinel) 32 to 2534 0 to 1390 2.5 1.4 0.01%/ °C 1.4 0.78 32 to 356 356 to 3344 3344 to 4515 0 to 180 180 to 1840 1840 to 2490 6.3 4 11.7 3.5 2.2 6.5 0.
® Minitrend GR 16 Options Specification Pulse Input (optional) 4 isolated inputs per board, frequency – 1Hz to 25kHz, updated once per sec. Input: Low < 1V, High >4V to <50V or Volt free input: Low = short circuit, High = open circuit. Alarm Outputs (optional) Programmable alarm set points (6 per pen) can be configured to activate up to 16 outputs. Update rate: 200 ms for all alarms. Number/Type: • 4 or 8 relay contacts SPDT, 3A 240VAC, 3A 24VAC/DC, 0.
® Minitrend GR Connections 17
® Minitrend GR Installation 18
® Minitrend GR 19 Model Selection Guides are subject to change and are inserted into the specifications as guidance only. Prior to specifying or ordering a model check for the latest revision Model Selection Guides which are published at: www.honeywellprocess.com/paperless-recorders Model Selection Guide (34-XY-16-10) Trendview Minitrend Recorder Model Selection Guide 43-TV-16-10 The Minitrend represents the latest in data acquisition and recording.
® Minitrend GR 20 TVMIGR TABLE V - FIRMWARE CREDITS/OPTIONS Standard Passwords ESS (Permanent Password Capability) None Five Credits Ten Credits Security/Firmware Twenty Credits Credits Thirty Credits Forty Credits Fifty Credits Sixty Credits Seventy Five Credits Ninety Nine Credits Future None Selection Availability 0__ S__ _0_ _ F_ _1_ _2_ _3_ _4_ _5_ _6_ _7_ _9_ __0 CREDITS - Decide what functions are needed and select that many total "Credits" when ordering firmware options.
® Minitrend GR 21 TVMIGR TABLE VII Factory Use Only Grey Color Bezel, Standard Honeywell labeling Black Color Bezel, Standard Honeywell labeling RESTRICTIONS Restriction Letter Table Available Only With Selection f g Table I I Selection Availability 000 014 Not Available With Selection 0_ 0 _, 4 _, P _ Notes: 1. Standard inputs include T/C, mV, V, Ma, Ohms and RTD actuations. 2. Relay Outputs are high level outputs (240VAC/3 Amp non-inductive loads). 3.
Sales and Service For application assistance, current specifications, pricing, or name of the nearest Authorized Distributor, contact one of the offices below. ASIA PACIFIC EMEA AMERICA’S Honeywell Process Solutions, (TAC) hfs-tacsupport@honeywell.