Use and Care Manual
GENSD55 6,000 Surge Watts/5,500 Running Watts Diesel Generator 11
Step 2 - Ground the Generator
Failure to properly ground this generator can result in electrocution.
Ground this generator by tightening the grounding nut against a grounding wire (Figure 3), found on the front of the battery. A No. 12 AWG
(American Wire Gauge) stranded copper wire is generally an acceptable grounding wire. The other end of this grounding wire should be connected
to a copper or brass-grounding rod that is driven into the earth.
Grounding codes can vary by location. Contact a local electrician for information on grounding regulations
for your area.
Step 3 – Install Battery (Not included)
This generator requires a battery to start. The generator does not come equipped from the factory with a battery.
A 12 Volt motorcycle battery no larger than 7 3/4” L x 5 1/4” H x 7 ¼” W, with a 360 Minimum CCA (Cold Cranking Amps). Comparable
brands/models are Husky: GT-X or Interstate: SP-35. These are not the only brands compatible with this generator. Any brand with similar specs
may be used. The battery may be smaller in size, and have a higher CCA.**Brands/model numbers can change, this information is intended as
a guide only, if your sparkplug needs to be replaced, please visit your local auto parts store for their recommendation, or call
1-866-460-9436 Monday - Friday, 8 AM - 4 PM Central Time for customer service for assistance**
The battery case is located behind the metal plate under the electrical panel. Install the battery by
using the two cables (one red and the other black) that were included in the packaging, or are
attached to the generator.
Disconnect all electrical loads from this generator before changing the battery.
1. Attach the end of the red cable to the positive/red terminal on the battery.
2. Attach the end of the black cable to the negative/black terminal on the battery.
3. Bolt the battery to the battery plate.
STARTING THE GENERATOR
STOP!
Before starting this generator, confirm that all the steps in the section titled, “Preparing the Generator for Use,” of this manual have been
correctly completed. If unsure about how to perform any of these steps, call 1-866-460-9436, Monday - Friday, 8 AM - 4 PM Central Time for
customer service.
If the generator has been used before, always check the oil level and diesel fuel level.
Always check that the battery is secure and the generator has been grounded.
To start this generator:
1. Confirm that there are no electrical devices connected to this generator.
2. Confirm that this generator is properly grounded. (See “Ground the Generator”)
3. Move Circuit breaker to OFF position. (Figure 6)
4. Set the engine Run switch to the “Run” position (Figure 6A).
5. Insert Key and turn it to the start position. (Figure 6B).
6. If the engine fails to start, repeat step 6. NOTE: After repeated attempts, consult the
Troubleshooting Guide before attempting again. (You may need to open top panel and
push down on Decompression Lever.)
If problems persist, call 1-866-460-9436, Monday - Friday, 8 AM - 4 PM Central Time.
7. Allow this generator to run for 3-5 minutes before connecting any electrical devices.
8. Move Circuit breaker to ON position.
9. Determine if you will use 120V or 120V/240V.
Move the Toggle Switch left or right to the correct setting (Figure 6D)
Figure 3
Figure 6C
Step 3 Battery Location
Figure 6B
Figure 6A
Ground
Figure 6
Figure 6D