Installation Manual

15
Wireless Network Specications
The thermostat will attempt to pair with the rst Basemodule it
“hears”. Do not attempt to create more than one “pair at the same
time in the same place.
To ensure paring success, place the T731W/O within a few feet of
the Base module while pairing. Once paired, the signal strength
tech menu can be used to ensure a robust wireless connection.
Placing either device in or around large metal objects can severely
degrade the wireless range.
The wireless network will automatically recover in the event of a
power loss or temporary signal loss.
Duration of
Occupancy
(Only displayed if
Local Occupancy
Sensor is ON)
Tech Setup Steps
Adjustment Options Default
LCD Will Show
Local
Occupancy
Sensor
When using the Occupancy model
the installer can choose to utilize
the occupancy sensor to set back
the room temperature while it is
not being occupied.
Set the heating temperature and
fan operation that you would like
the system to be while the space
is being occupied.
Full temperature ange dened
by setpoint limits.
First adjust the temperature
using the + and – buttons.
Use the Fan button to change
the fan operation.
Set the cooling temperature and
fan operation that you would like
the system to be while the space
is being occupied.
When the occupancy sensor is
turned on you have the ability
to set how long the thermostat
will go into occupancy mode
everytime a person is sensed.
30 = 30 minutes, 1 = 1 hour,
2 = 2 hours, 3 = 3 hours, 4
= 4 hours, 5 = 5 hours, 6 =
6 hours, 7 = 7 hours, 8 =8
hours, 9 = 9 hours, 10 = 10
hours, 11 = 11 hours, and 12
= 12 hours.
8
Full temperature ange
dened by setpoint limits.
First adjust the temperature
using the + and – buttons.
Use the Fan button to change
the fan operation.
Set the cool temperature and fan
operation that you would like the
system to be while the space is
unoccupied.
Full temperature ange dened
by setpoint limits.
First adjust the temperature
using the + and – buttons.
Use the Fan button to change
the fan operation. normal high
intensity all the time.
Occupancy Models Only
ON
OF(OFF)
OF
Occupied
Cool Setting
(Only displayed if
Local Occupancy
Sensor is ON)
78˚
Occupied
Heat Setting
(Only displayed if
Local Occupancy
Sensor is ON)
70˚
Unoccupied
Cool Setting
(Only displayed if
Local Occupancy
Sensor is ON)
83˚
Occupancy
Sensitivity
Setting
(Only displayed if
Local Occupancy
Tech Setup Steps
Adjustment Options Default
LCD Will Show
Set the heat temperature and fan
operation that you would like the
system to be while the space is
unoccupied.
Set the level of sensitivity of
the occupancy sensor. Lowering
the sensitivity will cause the
sensor to respond only to larger
movements.
High Sensitivity:
This is the most sensitive
setting and
will detect very slight mo-
tions. This is the recommend-
ed setting because it will work
well for nearly all applications.
Will detect any movement.
Medium Sensitivity:
This is the medium sensitive
setting and can be used
without pets setting it o.
Low Sensitivity:
This is the least sensitive
setting and can
be used in areas of major or
large motions. This will not be
set o by pets, small children,
or people more than 20’ from
the sensor location.
HI
Occupancy Models Only
Full temperature ange
dened by setpoint limits.
First adjust the temperature
using the + and – buttons.
Use the Fan button to
change the fan operation.
Unoccupied
Heat Setting
(Only displayed if
Local Occupancy
Sensor is ON)
62˚
Technician Setup
Technician Setup
16
Specications
0F
OCC SENSOR
8
OCC LENGTH
75
OCC COOL
70
OCC HEAT
83
UNOCC HEAT
62
UNOCC COOL
HI
19
Network Specications
A single basemodule can support up to 7 remotes.
If more than one Tthermostat is connected to a base module, the
system will control to the last interaction
Thermostat units will require up to 60 seconds to reect changes
elsewhere in the network.
A base module paired with another base module will work as a
“repeater”. It will match the relay state of the main base module.
Network Capabilities
Specications
The display range of temperature ... 41˚F to 95˚F (5˚C to 35˚C)
The control range of temperature.... 44˚F to 90˚F (7˚C to 32˚C)
Load rating.................................................1 amp per terminal, 1.5 amp
maximum all terminals combined
Swing (cycle rate or dierential) ...... Heating is adjustable from 0.2˚ to 2.0˚
Cooling is adjustable from 0.2˚ to 2.0˚
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz
for hardwire
Battery power from 2 AA Alkaline
batteries
Operating ambient ............................... 32˚F to +105˚F (0˚C to +41˚C)
Operating humidity .............................. 90% non-condensing maximum
Dimensions of thermostat ................. 4.7”W x 4.4”H x 1.1”D
Frequency ................................................ 916 MHz
Thermostat
Load rating ............................................... 1 amp per terminal, 1.5 amp
maximum all terminals combined.
Power source ...........................................18 to 30 VAC, NEC Class II, 50/60 Hz
Operating ambient ............................... 32˚F to +150˚F (0˚C to +65˚C)
Operating humidity .............................. 90% non-condensing maximum
Base Module
20
Changes or modications not expressly approved by the manufacturer could
void the user’s authority to operate the equipment.
Note: