Operating instructions
13 
Link Vent 1 to 
Override Inp (NO) 
Use this setting if any override inputs are in use. Override inputs can come from the use of a Weather Station, or 
other external device. 
Mx Vent Pos 
on Override 1 (CL) 
If a link is made to override input, the system will then ask what the maximum vent position should be during that 
override input period. 
Vent 1 Stg (1) 
On Immed Dehum 
Vent 1 Stg (1) 
On Delay Dehum 
Set the desired stages of operation here that will be activated by the dehumidify functions. You may choose either 
the IMMEDIATE or the DELAYED dehumidify functions, or both, for a particular stage. This setup is not applicable 
to “PAD VENT”. 
Vent 1 Stages 
(2
o
Sep.) 2
o
 Dif. 
Set the desired separation of the ventilation stages here, and also the desired differential. The separation is the 
total number of degrees that separate each stage of operation. Once an output or a stage has been activated the 
differential is the amount of temperature change required that the will cancel the operation of that stage or output. 
This setup is not applicable to “PAD VENT”. 
Vent 1 Timing 
(2 Sec.) 
Set the desired time delay here. The time delay will be active on both energizing and de-energizing stages. This 
setup is not applicable to “PAD VENT”. 
Reference Temp: 
(Sensor Selection) 
(IF USED) 
Min Ref (0
o
) 
Go To (0%) Normal 
Max Ref (70
o
) 
Go To (100%) Normal 
Use this selection to enter a reference temperature for the vent system. For example, select the outdoor sensor, 
then enter a minimum and maximum reference temperature, and a minimum and maximum ventilation position.  
The Procom will then constantly adjust the ventilation position based on the outdoor temperature.