Operating instructions
20 
SET DEHUMIDIFY 
The SET DEHUMIDIFY
mode is used to enable or to disable the dehumidify functions of the control. The run time 
of the immediate and the delayed dehumidify functions are set here. The repeat time of the dehumidify feature is 
set here. The dehumidify differential, and the maximum heat loss and gain for the dehumidify mode are also 
entered here. 
1. Enter the SET DEHUMIDIFY mode. 
2. Use the PRIOR-NEXT switch to advance to the desired item to set. 
3. Use the VALUE switch to toggle between desired choices that the system has internally provided. 
Dehum 1 
(Disabled) 
You may select how to disable the dehumidify feature. Dehumidify may be disabled upon an override input. The 
dehumidify feature can be disabled all together if desired. 
Dehum 1 Imm 
Run time (10) Min 
Enter the time to allow Immediate Dehumidify to run. 
Dehum 1 Dly 
Run Time (10) Min 
Enter the time to allow Delay Dehumidify to run. 
If Dehum Fails 
Rpeat in (2:00) H 
Enter the time to repeat the dehumidify if unable to lower the humidity. If you would like the Procom to constantly 
stay in the dehumidify mode if the humidity level is high, without an interruption, enter “Stay in Dly Mode”. 
Dehum 1 Dif. 
(2)% RH 
Set the desired differential for dehumidify. The differential is the amount of humidity decrease that the sensor 
must see before disabling dehumidify. 
Disable Dehum if 
below HtSP by (5)
o 
Set the maximum heat loss below the normal heating set point temperature. This will disable any cooling stages 
activated during dehumidify. This prevents too much heat loss in the range during dehumidify. 
Disable Dehum if 
above HtSP by (5)
 o
Set the maximum heat gain above the normal heating set point temperature. This will disable any heating stages 
activated during dehumidify. This prevents too much heat gain in the range during dehumidify. 