Technical data
Procon
. LMU C, F I (’)
If the optional QAA Room Unit, RVA Cascade Controller, or 
RVA Zone Controller has been connected to the boiler, and a fault 
occurs, the  or ER will appear on the display of the respective Unit 
as well as the boiler.
The Error message can be reviewed at the QAA Room Unit, RVA 
Cascade Controller, or RVA Zone Controller, by opening the hinged 
 ap and pressing the ‘DOWN’ Program button twice. ID Line  will be 
displayed on the ‘Left-Hand’ side, with the error message on the ‘Right-
Hand’ side of the display.
To clear the error message the ‘RESET’ button on the boiler must be pressed, the error message CAN NOT be 
cleared at the Room Unit, or RVA controller.
. R LMU O I
To aid the End User and/or the Installation/Commissioning Engineer, the operating information of the boilers’ 
LMU controller can be access and reviewed as follows;
Press the INFO button, then Press & Hold the 
▲ & ▼ buttons until b appears (approximately  seconds).
Use the + & - buttons to review the b references, use the 
▲ or ▼ buttons to change from b, to c & d references.
Press the MODE button at any time to return to the normal display.
The table below details the references and their meanings;
Ref Description Ref Description Ref Description
b Current Fault Code c No Function d No Function
b Actual Return Temp (°C) c
Actual Recti cation Current
(µAmps)
d
Theoretical Value for Flow Temp
(°C)
b Actual HWS Temp (°C) c
Actual Fan Speed
{XX ×  = Actual Revs/Min}
d
Actual Target Value for Flow Temp
(°C)
b Actual Flue Gas Temp (°C) c Actual PWM Drive Signal to Fan () d Room Temp Target Value (°C)
b
Actual Outside Air Temp
(°C)
c
Actual Boiler Output  Relative to 
Maximum rate
d
HWS Temp Target Value
(°C)
b Averaged Outside Air Temp (°C) c
Actual PWM Output to Modulation 
Boiler Pump (Not Used)
d
Maximum Modulation Depth of 
Boiler ()
b
Attenuated Outside Air Temp
(°C)
c No Function d
Maximum Fan Speed / Power 
Output of Boiler
b
Actual Flow Temp of Mixed Circuit, 
when AGU. Clip Used (°C)
c No Function d No Function
b No Function c No Function d No Function
b No Function c No Function d No Function
. R LMU O E C
As an extension of the Standard ERROR Codes, the LMU also records Operating ERROR Codes, which can 
be accessed by at Service / Commissioning Engineer.
To access the Operating ERROR Codes, ‘Press & Hold’ the 
▲
 & 
▼
 Buttons, for approximately  seconds. H  will 
appear, then use the ▲ or ▼ Buttons to reference the Parameter Line ID Number detailed below.
Line ID 
Number
Description Comments
H st Historical Fault – Number of Occurrences
The number of times that this Operating Error Code as shown in 
Parameter H has occurred
H st Historical Fault – Operating Phase
The position during the operating sequence that the Operation 
Error occurred
H st Historical Fault – Operating Error Code Actual Operating Code. Refer to Section .
H nd Historical Fault – Number of Occurrences
The number of times that this Operating Error Code as shown in 
Parameter H has occurred 
H nd Historical Fault – Operating Phase
The position during the operating sequence that the Operation 
Error occurred.
Sequence 
Number
Description
 Fan operating at pre-purge rate
 Ignition spark generation
 Gas valve activation
Flame stabilization and 
recti cation
 Burner released to modulate