General Specifications
Electrical Specifications
Environmental Specifications
DC model AC model
Power Supply
Input Voltage DC24V AC100 to 240V
Rated Voltage DC19.2 to 28.8V AC85 to 265V
Allowable Voltage Drop 10ms (max.)
1 cycle or less
(Voltage drop interval
must be 1s or more.)
Power Consumption 45W (max.)
AC100V 0.90A or less
(TYP 0.48A)
AC240V 0.45A or less
(TYP 0.26A)
In-Rush Current 30A (max.) 60A (max.)
Voltage Endurance
AC1000V 20mA for
1 minute (between
charging and FG
terminals)
AC1500V 20mA for
1 minute (between
charging and FG
terminals)
Insulation Resistance
DC500V 10M (min.) (between charging and FG
terminals)
Physical
Surrounding Air
Temperature
0 to +50°C
Storage
Temperature
-20 to +60°C
Ambient Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Storage Humidity
10 to 90% RH
(Wet bulb temperature: 39°C max. - no condensation.)
Dust 0.1mg/m
3
and below (non-conductive levels)
Pollution Degree For use in Pollution Degree 2 environment.