User guide
GP3000 Series Hardware Manual
5-4
Output Specifications (Sink type)
Output Circuit (Sink type)
Rated Voltage DC 24V
Rated Voltage Range DC 20.4V to DC 28.8V
Output Method Sink Output
Maximum Load Voltage 0.2A /point, 0.4A /common
Output Voltage Drop 1.5V or less
Output Delay Time
OFF to ON: 1ms or less
ON to OFF: 1 ms or less
Voltage Leakage (when OFF) 0.1mA or less
Clamp Voltage 39V ±1V
Type of Output Transistor Output
Common Lines 1
Common Design 2 points/1 common line
External Connection 12-pin connector (also used for Input)
Output Protection Type Output is unprotected
Internal Fuse 1.5A, 125V DIP fuse (not replaceable)
Surge Control Circuit Zener diode
Output Points 2
Output Signal Display No LED indicators
Status Display Element None
Isolation Method Photocoupler Isolation
External Power Supply DC 24V
• Since the output terminals are not electrically protected, an output line might be short-circuited
or a connection fault might damage the GP unit. Please install an applicable fuse to prevent an
overload in the circuit, if necessary.
L
L
+24V B1
OUT1 A2
0V A1
OUT0 B2
Internal Circuit
Internal Circuit
Fuse 1.5A
DC 24V
External Power
+
-