*3 + 6HULHV +DUGZDUH 0DQXDO
Preface Thank you for purchasing Pro-face's GP3000H Series Programmable Operator Interface (Hereafter referred to as the “GP unit”). Before operating your GP unit, be sure to read this manual to familiarize yourself with the GP unit's operation procedures and features. NOTICE 1. Copying this manual's contents, either in whole or in part, is prohibited without the express permission of Digital Electronics Corporation, Japan. 2. The information contained in this manual is subject to change without notice.
Essential Safety Precautions All safety-related procedures stated in this document must be followed to operate the GP correctly and safely. Be sure to read this and any related documents thoroughly to understand the correct operation and functions of the GP unit. Safety Icons Throughout this manual, these icons provide essential safety information for GP operation procedures requiring special attention.
When using the GP with transportation vehicles (trains, cars, and ships), disaster and crime prevention devices, various types of safety equipment, and medical devices that are not life-support related, use redundant and/or failsafe system designs to ensure proper reliability and safety. After the GP unit's backlight burns out the touch panel is still active, unlike the GP unit's "Standby Mode".
Installation Be sure all cable connectors are securely attached to the GP unit. A loose connection may cause incorrect input or output signals. Wiring Be sure to ground the GP unit's FG wire separately from other equipment FG lines. Also, be sure to use a grounding resistance of 100Ω or less and a 2mm2 or thicker wire, or your country's applicable standard. Otherwise, electric shock or malfunctions may result. Be sure that metal particles and wiring debris do not fall inside the GP unit.
Do not operate or store the GP in locations where it can be exposed to direct sunlight, high temperatures, excessive dust, moisture or vibration. Do not operate or store the GP where chemicals evaporate, or where chemicals are present in the air. Corrosive chemicals: Acids, alkalines, liquids containing salt Flammable chemicals: Organic Solvents Do not use paint thinner or organic solvents to remove dirt or oil from the GP unit's surface. Instead, use a soft cloth moistened with a diluted neutral detergent.
• Extended shadows, or “Crosstalk” may appear on the sides of screen images. This is an LCD characteristic and not a product defect. • The color displayed on the GP unit's LCD screen may appear different when seen from outside the specified viewing angle. This is an LCD characteristic and not a product defect. • When the same image is displayed on the GP unit's screen for a long period, an afterimage may appear when the image is changed. This is an LCD characteristic and not a product defect.
Information Symbols This manual uses the following icons: Indicates a warning or a product limitation. Be sure to follow the instructions given with this icon to ensure the safe operation of the GP. Screen Editor Indicates the GP-Pro EX software. PLC Abbreviation for Programmable Logic Controller. * Indicates useful or important supplemental information. Contains additional or useful information. SEE Indicates pages containing related information.
GP3000H Series Model Name Indication Model name A G P 3 * **H - * 1 - *** - **** A B A 3 B 00 10 L S T D24 None C D E C D E 5.7-inch AGP-3300HL/AGP-3300HS: QVGA (320 x 240 pixels) AGP-3310HT: VGA (640 x 480 pixels) Standard machine Monochrome LCD STN color LCD TFT color LCD DC type power supply is used.
Package Contents The following items are included in the GP unit's package. Before using the GP, please check that all items listed here are present. GP Unit: 1 • English and Japanese Installation Guides (1 of each) Hand Strap: 1 Hanger: 1 (Attached to the GP unit) The hanger is used to hang the GP unit on a wall.
Installation prerequisites for standards • UL listed products*1 Industrial Control Equipment refer to UL508 see [a] in the “Product List“ refer to CSA-C22.2 No.142 see [b] in the “Product List“ • c-UL listed products*1 Standard for Process Control Equipment • Product List Product Model No. Registration Model No. UL c-UL [a] [b] AGP3300H-L1-D24 3610005-03 9 9 AGP3300H-S1-D24 3610005-02 9 9 AGP3310H-T1-D24 3610005-01 9 9 UL/c-UL File No.
Contents Preface ...................................................................................................................... 1 Essential Safety Precautions..................................................................................... 2 Information Symbols.................................................................................................. 7 About the Manuals ....................................................................................................
2.3.1 Serial Interfaces...................................................................................................2-8 2.3.2 Ethernet Interface ................................................................................................2-9 2.3.3 DC24V Interface ..................................................................................................2-9 2.3.4 3-Position Enable Switch Output Interface ........................................................2-12 2.3.
1 Overview 1. System Design 2. Accessories 3.
GP3000H Series Hardware Manual 1.1 System Design The following diagram illustrates the standard range of items that can be connected to GP-3000H Series unit. For host controller (PLC, etc.) connection information, refer to the "GP-Pro EX Device/PLC Connection Manual".
Chapter 1 Overview GP Unit – Continued from the GP3000H Cable Connector (8) (3) GP3000H Hard-type 10 m Direct-connect Cable (with connector) GP3000H-CBLHD-10M RS-232C Cable CA3-CBL232/5M-01 GP3000H Conversion Adapter AGP3000H-ADPCOM-01 (8) Mitsubishi PLC Q-Series Link Cable CA3-CBLLNKMQ-01 (8) GP3000H Soft-type 5 m Direct-connect Cable (with connector) GP3000H-CBLSD-5M Omron PLC SYSMAC Link Cable CA3-CBLSYS-01 (8) GP3000H Soft-type 10 m Direct-connect Cable (with connector) GP3000H-CBLSD-10M Mit
GP3000H Series Hardware Manual GP Unit – Continued from the GP3000H Cable Connector (3) Continued from GP3000H Conversion Adapter (6) MPI Cable ST03-A2B-MPI21-PFE Mitsubishi PLC FX-Series Connection Cable CA3-CBLFX/1M-01 CA3-CBLFX/5M-01 Mitsubishi PLC A-Series Connection Cable CA3-CBLA-01 (10) (11) (11) (9) RS-422 Cable CA3-CBL422/5M-01 COM Port Conversion Adapter CA3-ADPCOM-01 RS-422 Cable CA3-CBL422-01 (11) 2 Port Adapter Cable CA3-MDCB11 Mitsubishi PLC A, QnA, FX Series' 2 Port Adapter II GP070
Chapter 1 Overview DC24V GP Unit – Continued from the GP3000H Cable Connector (8) (3) GP3000H Soft-type 3 m Cable for GP2000H Conversion Adapter (with connector) GP3000H-CBLSD232-3M*4 GP2000H RS-232C Conversion Adapter GP2000H-AP232 RS-232C Cable GP410-IS00-O*5 Host Controller PLC etc.
GP3000H Series Hardware Manual Edit Mode Peripherals To an Ethernet Network GP Unit (1) GP3000H Hard-type 10 m Direct-connect Cable GP3000H-CBLH-10M GP3000H Soft-type 5 m Direct-connect Cable GP3000H-CBLS-5M GP3000H Soft-type 3 m Direct-connect Cable GP3000H-CBLS-3M GP3000H Soft-type 10 m Direct-connect Cable GP3000H-CBLS-10M (2) HUB (Commercial type) USB Port USB Transfer Cable CA3-USBCB-01 USB Memory Strage*1 (Commercial type) Serial Port USB-Serial (RS-232C) Conversion Cable CA6-USB232-01 RS-
Chapter 1 Overview 1.1.1 Restrictions Please be aware of the following restrictions when using the GP2000H RS-232C/RS-422 Conversion Adapter (Hereafter referred to as the "GP2000H Conversion Adapter") to connect the GP3000H to peripheral equipment. • The GP3000H cannot be connected to Ethernet networks. • For GP3000Hs mounted with key switches, outputting to peripheral equipment by turning the GP3000H key switch is not possible.
GP3000H Series Hardware Manual 1.2 Accessories All accessories listed here are produced by Pro-face. 1.2.1 GP3000H Cable Connector Accessories for connecting the external devices to GP3000H directly Product Name Model No.
Chapter 1 Overview Accessories for connecting GP2000H Series RS-232C or RS-422 Conversion Adapter to GP3000H Product Name GP3000H Soft-type 3 m Cable for GP2000H Conversion Adapter (with connector)*1 GP3000H-CBLSD232-3M GP3000H Soft-type 10 m Cable for GP2000H Conversion Adapter (with connector)*1 GP3000H-CBLSD232-10M GP2000H Series RS-232C Conversion Adapter *1 GP2000H-AP232 GP3000H Soft-type 3 m Cable for GP2000H Conversion Adapter (with connector) *1 GP3000H-CBLSD422-3M
GP3000H Series Hardware Manual 1.2.3 CF Card Items Product Name 1.2.4 CF Card (128MB) CA3-CFCALL/128MB-01 CF Card (256MB) CA3-CFCALL/256MB-01 CF Card (512MB) CA3-CFCALL/512MB-01 CF Card (1GB) CA6-CFCALL/1GB-01 CF Card (2GB) CA8-CFCALL/2GB-01 CF Card Adapter GP077-CFAD10 Description Inserted into the GP unit's CF Card slot. Used for read/write of CF Card data via a PC's PCMCIA slot. Option Items Product Name 1.2.5 Model No. Model No.
Chapter 1 Overview Product Name Model No. Description Mitsubishi PLC Q-Series Link Cable CA3-CBLLNKMQ-01 (5m) Connects Mitsubishi PLC Q-Series (or other host controller) to this adapter. (RS-232C) Omron PLC SYSMAC Link Cable CA3-CBLSYS-01 (5m) Connects Omron PLC SYSMAC Series unit (or other host controller) to this adapter. (RS-232C) CA3-CBLA-01 (5m) Connects Mitsubishi PLC A, QnA Series programming console I/F to this adapter. (Simultaneous use of programming console is not possible.
GP3000H Series Hardware Manual 1.2.7 Maintenance options for the GP3000H Conversion Adapter Accessory to the GP3000H Conversion Adapter. Sold separately as an option for maintenance. Product Name Installation Gasket 1.2.8 RS-232C Cable *1 SEE Provides dust and moisture resistance when GP3000H Conversion Adapter is installed into a solid panel. Model No. GP410-IS00-0*1 Description Connects the GP2000H Series RS-232C Conversion Adapter and Host (PLC). Certain types and models of PCs cannot be used.
Chapter 1 Overview 1.3 Part Names and Functions A: Status LED (POWER) This LED indicates the GP's status, e.g. power input, firmware RUN status or backlight condition. E Color Indicator A B C Operation Mode OFFLINE Green ON Red ON When power is turned on. ON Backlight burnout or GP malfunction*1 Flashing During software startup Orange In operation OFF *1 D Front Power is OFF. When backlight replacement or repair of the GP is required, please contact your local GP distributor.
GP3000H Series Hardware Manual H: USB Host Interface Complies with USB 1.1. Uses a “TYPE-A” connector. Power supply voltage: DC5V±5%, Output current: 500 mA (max). Connect to the transfer cable, storage device (USB memory, CF Card reader), etc. The maximum communication distance: 5 m. CF Card Cover Open G I: CF Card Interface Insert the CF Card in this slot.
Chapter 1 Overview G L F L: Hanger A hanger for temporarily hanging the GP unit on a wall. M Q R N • Do not operate or conduct wiring of the GP unit, with the GP unit hung on a wall. Otherwise, the GP may fall, resulting in injury or damage to the equipment. T O P O S Rear Right Side • The following is recommended to be used as pairs for this hanger; -A ϕ7 or less, rod-shaped or S-shaped hook -M4 pan-head machine screw with head diameter ϕ7 or less. -Panel thickness: 1 to 1.6mm [0.04 to 0.06 in.
GP3000H Series Hardware Manual 1-16
2 Specifications 1. General Specifications 2. Performance Specifications 3. Connection with Peripheral Equipment 4. Dimensions This chapter describes the general, functional and interface specifications of the GP as well as its dimensions.
GP3000H Series Hardware Manual 2.1 General Specifications Electrical Specifications Power Supply 2.1.1 2.1.2 Input Voltage DC24V Rated Voltage DC19.2 to 28.8V Allowable Voltage Drop 10 ms (max.) Power Consumption 16.7 W (max.) In-Rush Current Voltage Endurance AC500V 20 mA for 1 minute (between charging and FG terminals) Insulation Resistance DC500V 10 MΩ (min.
Chapter 2 Specifications External Specifications Installation 2.1.3 Grounding Grounding resistance of 100 Ω 2 mm2 or thicker wire, or your country's applicable standard. (Same for FG and SG terminals) Structure *1 Rating: Equivalent to IP65f Cooling Method Natural air circulation Weight Approx. 1,000g [2.2 lb.] max. (GP without a Key Switch, unit only) 1,050g [2.3 lb.] max. (GP with a Key Switch, unit only) External Dimensions *1 W 224 mm [8.82 in.] X H 174 mm [6.85 in.] X D 87.1 mm [3.43 in.
GP3000H Series Hardware Manual 2.2 Performance Specifications 2.2.1 Performance Specifications Application*1 External Output I/F*4 GP3000H Cable Connector Data Backup SRAM 320 KB (Used lithium battery for backup memory) Serial Interface RS-232C/RS-422/RS-485 Asynchronous Transmission: Data Length: 7 bit/8 bit Parity: none, Odd or Even Stop Bit: 1 bit/2 bit Data transmission Speed:2400 bps to 115.2 kbps 187.
Chapter 2 Specifications *1 User active capacity. *2 When using the GP3000H Conversion Adapter, the distance includes the length of cable between the GP and the Conversion Adapter. *3 Overall system may not meet these standards if implemented outside these parameters. Be sure to follow these standards when designing the system. *4 To use GP's external output interface eg.
GP3000H Series Hardware Manual 2.2.2 Display Specifications Display Type Resolution AGP-3300HL AGP-3300HS Monochrome LCD STN Color LCD W 320 X H 240 pixels Dot pitch W 0.36 mm [0.01 in.] X H 0.36 mm [0.01 in.] Effective Display Area W 117.2 mm [4.61 in.] X H 88.4 mm [3.48 in.] Color/Shade level Black and White (16 Shades) 4,096 Colors AGP-3310HT TFT Color LCD W 640 X H 480 pixels W 0.18 mm [0.01 in.] X H 0.18 mm [0.01 in.] W 115.2 mm [4.54 in.] X H 86.4 mm [3.40 in.
Chapter 2 Specifications 2.3 Connection with Peripheral Equipment • To use GP's external output interface eg. DOUT and build a system, Pro-face's dedicated Cable with Connector and Conversion Adapter (AGP3000H-ADPCOM01) (separately sold) are required. • For the details of DOUT circuit diagram, etc..., please see "GP3000H Conversion Adapter Installation Guide" (Included with the Conversion Adapter) • For the kinds of the dedicated Cable with Connector, please see "1.2 Accessories 1.2.
GP3000H Series Hardware Manual 2.3.1 Serial Interfaces This interface is used to connect an RS-232C/RS-422/RS-485*1 cable. Connect to the D-SUB 9-pin plug type connector. For host controller (PLC, etc.) connection information, refer to the “GP-Pro EX Device/PLC Connection Manual”. Recommended Cable Connector XM2D-0901 Recommended Cable Cover XM2S-0913 Recommended Jack Screw #4-40 (UNC) XM2Z-0073
Chapter 2 Specifications • If isolation is required, use the RS-232C isolation unit (CA3-ISO232-01) by Pro-face, and the following recommended equipment. Recommended Intermediate Connector Recommended Fastener 1 Recommended Cable Cover 2.3.2 XM2A-0901 XM2Z-0003 XM2S-0913 Ethernet Interface Ethernet (IEEE802.3u, 10BASE-T/100BASE-TX) with modular jack connector (RJ-45) 2.3.
GP3000H Series Hardware Manual Connecting the Power Supply This section describes the precautions for supplying a power voltage. Twisted-pair cord Constant Voltage Transformer • If the supplied voltage exceeds the GP unit’s range, GP FG connect a constant voltage transformer. SEE Chapter 2 Specifications (page 2-1) • For between the line and ground, select a power Twisted-pair cord Insulating Transformer supply that is low in noise.
Chapter 2 Specifications Grounding This section describes the precautions for grounding the GP unit. Do not use common grounding, since it can lead to an accident or machine breakdown. (a) Exclusive Grounding (BEST) • When supplying power to the GP unit, be sure to separate the Other Equipment GP input/output and power lines, as shown. [diagram (a)] • Check that the grounding resistance is 100Ω or less. • FG and SG terminals are internally connected in the GP.
GP3000H Series Hardware Manual 2.3.
Chapter 2 Specifications With the GP unit incorporating an emergency switch, the emergency switch activates the contact output, when the emergency switch is enabled. To reset the emergency stop status (lock status), pull the button forward, or turn the button in the direction indicated by arrow. When the emergency switch is pressed, ON/OFF status of the EMG0 to EMG2 signals are as follows: ( ) indicates contact status.
GP3000H Series Hardware Manual 2.3.7 Connecting the GP Unit • Always connect the connection device side first, and the GP side last. Failure to observe this precaution may damage the RS-232C/RS-422/RS-485 circuitry. Attachment (1) Before connection, remove the cable’s connector cap and GP3000H connector cover. To remove the cable’s connector cap, pull out the cable by holding the cable connector as shown. Pull out the cable by holding the cable connector.
Chapter 2 Specifications Removal (1) Unlock the connector that has been locked in the mounting procedure. (Turn the lock ring as shown so that the small U mark is displaced from the V mark). Then, pull out the cable by holding the cable connector. 2. Pull out the cable by holding the cable connector. 1. Turn the lock ring to unlock the connector. • To disconnect the cable, be sure to hold the cable connector and pull it out. If you hold other parts of the cable (lock ring, etc.
GP3000H Series Hardware Manual 2.4 Dimensions 2.4.1 Dimensions The following dimensions apply to GP3000H Series units. External Dimensions 87.1 [3.43] 107.5 [4.23] Unit: mm [in.] Top 174 [6.85] 224 [8.82] Front 2.4.2 External Dimensions of the Emergency Switch Guard 45 [1.77] 81.5 [3.21] Unit: mm [in.] 65 [2.
3 Fixing the GP and Attaching Accessories 1. Fixing the GP3000H 2. Instructions for Mounting Accessories 3. CF Card Insertion/Removal This Chapter explains methods for fixing the GP, and instructions for attaching accessories.
GP3000H Series Hardware Manual 3.1 Fixing the GP3000H This section explains cautions involved with handling the GP3000H Series units. Be sure to operate the GP unit only after securing it, using any of the following three methods. Be sure to use the hand strap or neck strap, or attach the GP unit to a wall with the Wall Mount Adapter. Dropping the unit may result in injury to the user or damage to the unit.
Chapter 3 Fixing the GP and Attaching Accessories 3.1.2 Neck Strap Attaching the Neck Strap The neck strap (optional) that attaches to the GP3000H Series unit is used to hang the GP unit from the user’s neck, and to prevent it from dropping during use. Attach the neck strap using the following procedure. (1) Start by removing the neck straps from the buckles on both ends as shown. Next, insert the ends of the neck straps into the neck strap mounting slots as shown.
GP3000H Series Hardware Manual 3.2 Instructions for Mounting Accessories 3.2.1 Attaching the Emergency Switch Guard An emergency switch conforms to safety standards (EC Machinery Directive IEC60204-1, etc.). When the emergency switch guard is attached, the emergency switch does not conform these standards. If conforming to the safety standards is required, do not use the emergency switch guard (included in the GP unit).
Chapter 3 Fixing the GP and Attaching Accessories 3.2.2 Replacing the Function Switch Sheets (1) There are two holes located on the lower right and left corners of the GP for replacing the function switch sheet. Remove the cover on the insertion hole, pull out the current sheet, and insert the new sheet (sold separately). • It’s easy to insert the function switch sheet with the edge bent on the dotted line as shown.
GP3000H Series Hardware Manual 3.3 CF Card Insertion/Removal This section describes how to insert and remove a CF Card. When using the GP Unit and a CF Card, observe the following precautions: Prior to inserting or removing a CF Card, be sure to turn the GP unit’s CF Card ACCESS switch OFF and to confirm that the ACCESS lamp is not lit. If you do not, CF Card internal data may be damaged or lost.
Chapter 3 Fixing the GP and Attaching Accessories 3.3.1 Inserting the CF Card Use the following steps to insert the CF Card in the GP. (1) Open the CF Card cover on the rear panel of the GP by pulling the tab as indicated by the arrow. (2) Insert the CF Card in the CF Card Slot, until the eject button is pushed forward. Set DIP Switch No. 4 to ON. Eject Button Set DIP Switch No. 4 to ON. • To make the CF Card accessible, set DIP Switch No. 4 to ON.
GP3000H Series Hardware Manual 3.3.2 Removing the CF Card Simply reverse the steps shown in the previous “Inserting CF Card” explanation. • Open the CF Card cover and set DIP Switch No. 4 to OFF. Confirm that the CF Card access LED goes out and then press the eject button to remove the CF Card. 3.3.3 CF Card Handling The CF Card has a data overwrite limit of approximately 100,000 times. Therefore, be sure to back up all CF Card data regularly to another storage media.
4 Maintenance 1. Cleaning the Display 2. Periodic Check Points 3. Replacing the Backlight This chapter explains cautions and inspection criteria that will ensure trouble-free use of the GP.
GP3000H Series Hardware Manual 4.1 Cleaning the Display When the surface or frame of the display become dirty, soak a soft cloth in water with a neutral detergent, wring the cloth tightly, and wipe the display. • Do not use paint thinner, organic solvents, or a strong acid compound to clean the unit. • Do not use hard or pointed objects to operate the touch-screen panel, since it can damage the panel surface.
Chapter 4 Maintenance 4.2 Periodic Check Points To keep your GP unit in its best condition, please inspect the following points periodically. GP Operation Environment Is the operating temperature within the allowable range (0ºC to 40ºC)? Is the operating humidity within the specified range (10%RH to 90%RH, dry bulb temperature of 39ºC or less)? Is the operating atmosphere free of corrosive gasses? When using the GP unit inside a panel, the ambient environment refers to the interior of the panel.
GP3000H Series Hardware Manual 4.3 Replacing the Backlight • The backlight in the GP3000H Series cannot be replaced by the user. When the backlight needs to be replaced, please contact your local GP distributor.