Manual

17
Input Circuit Drawings
Internal Circuit
Wiring
indicates a fuse. indicates load.
Since the output terminals are not electrically protected, an output line might be shortcir-
cuited or a connection fault might damage this product. Please install an applicable fuse to
prevent an overload in the circuit, if necessary.
Maximum Load
Voltage
Per Channel 0.3 A 0.1 A
Per Common 3 A 1 A
Output Protection Type Output is unprotected
Output Voltage Drop
1 VDC or less (voltage between COM and output
terminals when output is on)
Clamp Voltage 39 VDC ±1 V
Voltage Leakage (when OFF) 0.1 mA or less
Output Delay
Time
OFF-ON 300 µs or less
ON-OFF 300 µs or less
Isolation Method
Between output terminals and internal circuit:
photocoupler isolated
Between output terminals: not isolated
External Connection
10-pin terminal
connector
MIL connector
EXM-DDO8TT EXM-DDO16TK
Internal
Circuit
Output
L
<EXM-DDO8TT> <EXM-DDO16TK>
Q0 0
Q1 1
Q2 2
Q3 3
Q4 4
Q5 5
Q6 6
Q7 7
COM(+)
-V
20 Q0
Q1
Q2
Q3
Q4
Q5
Q6
Q7
COM(+)
2 -V
Q8 19
Q9
Q10
Q11
Q12
Q13
Q14
Q15
COM(+)
-V 1