Manual
18
15.4 8-point/16-point relay-output module
RELAY OUTPUTS WELDED CLOSED
• Always protect relay outputs from inductive alternating current load damage using an
appropriate external protective circuit or device.
• Do not connect relay outputs to capacitive loads.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EXM-DRA8RT EXM-DRA16RT
No. of Output Points
8 points
(4 points/1 common)
16 points
(8 points/1 common)
*1
*1 When connecting to Hybrid Terminal Block (HTB), up to 6 EXM-DRA16RT (up to 96 points
of the total output points of EXM-DRA16RT) can be connected. When connecting EXM-
DRA16RT up to 6, the following output modules cannot be connected to as the 7th module;
EXM-DRA8RT,EXM-DRA16RT, EXM-DDO8UT, EXM-DDO8TT, EXM-DDO16UK, EXM-
DDO16TK, EXM-DMM8DRT.
No. of Common 2
Output Method 1a-contact
Maximum
Load Voltage
Per Channel 2 A or less
Per Common 7 A or less 8 A or less
Maximum Load Voltage 0.1 mA/0.1 VDC (reference value)
Contact Rating
240 VAC, 2 A (resistance load, cos θ=0.4 induced
load)
30 VDC, 2 A (resistance load, L/R-7 ms induced load)
Initial Shorting Resistance 30 mΩ max.
Electrical Life
100,000 operations or more
(rated resistive load 1,800 operations/h)
Mechanical Life
20 million operations or more
(no load 18,000 operations/h)
Voltage Endurance
Between output to terminals: 1500 VAC, 1 minute
Between output terminal and internal circuit: 1500 VAC,
1 minute
Between output groups: 1500 VAC, 1 minute
Output Delay Time
External Connection 11-pin terminal connector 10-pin terminal connector
Command
Output
Relay
Status
OFF delay: 10 ms max.
Contact bounce: 6 ms max.
ON delay: 6 ms max.
ON
OFF
ON
OFF