Manual

20
15.5 4-point inputs/4-point relay-output module,16-point inputs/8-point relay-
output module
RELAY OUTPUTS WELDED CLOSED
Always protect relay outputs from inductive alternating current load damage using an
appropriate external protective circuit or device.
Do not connect relay outputs to capacitive loads.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
EXM-DMM8DRT EXM-DMM24DRF
Rated Input Voltage 24 VDC
Rated Input Voltage Range DC20.4 to 28.8 V
Rated Input Current
7.3 mA/input (when 24
VDC is applied)
7 mA/input (when 24
VDC is applied)
No. of Input Points
4 points (sink/source
type - dual use)
16 points (sink/source
type - dual use)
No. of Input Common 1
Input ON Voltage 15 VDC or higher
*1
Input OFF Voltage 5 VDC or less
*1
Input Impedance 3.3 k 3.4 k
Isolation Method
Between input terminals and internal circuit:
photocoupler isolated
Between input terminals: not isolated
Input Delay
OFF-ON 4 ms
ON-OFF 4 ms
Usage Limits No limits Limits
*2
External Load for I/O
Interconnection
Not needed
Signal Determination Method LED lights when each point turns ON (logical side)
No. of Output Points
4 points (4 points/1
common)
8 points
No. of Output Common 1 NO 2 NO
Output Method 1a-contact
Maximum Load
Current
*3
Per Channel 2 A or less
Per Common 7 A or less
Min. Open/Close Load 0.1 mA/0.1 VDC (reference value)