Manual

26
Connect a fuse appropriate for the applied voltage and current draw, at the position shown
in the diagram.
When the voltage input is open, the input into the unused channels is approx. 2.5 VDC for
revision
PV: 03 RL: 07 SV: 1.2” and 0 VDC for revision “PV: 04 RL: 08 SV: 2.0”.When
the voltage input is short circuited, 0 VDC is input to them. Please shortcircuite to
prevent from the invalid values input. When the current input is open, error code
(RGEF130 input data error) occurs to the unused channels, then the invalid values are
input. The voltage input settings is recommended to the unused channels.
The (-) poles of inputs IN0 and IN1 are connected internally.
15.7 4-ch Analog input / Temperature input module
The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated input
voltage ranges from DC19.2 to 30 V including ripple. The consumption current is 60 mA
(24 VDC) when the input is not-open, output 100%. You can input voltage, current, or
temperature probes on up to 4 channels. You cannot use different types of input at the same
time.
EXM-AMI4LT
Characteristics of Analog Voltage Inputs
Voltage Input Current Input
Temperature Probes
Input Range
DC0 to 10 V DC0 to 20 mA
(RTD)
Pt100/Pt1000/
Ni100/Ni1000,
3-wire type
Pt sensor: -200
to +600°C (-328
to +1112°F)
Ni sensor: -50 to
+150°C (-58 to
+302°F)
Input Impedance 10 k min. 250 max. 10 k min.
Input Points 4 points
A-D Conversion Sample
Repetition Time
160 ms
Total Input
System
Transfer Time*
1
4x160 ms + 1 scan time
8x160 ms + 1
scan time
Input Type Non differential input
Operating Mode Self-scan
Conversion Mode
 type ADC
Input Error Maximum Error
at 25°C (77°F)
±0.2% of full scale
±0.4% temperature probe input
Temperature
Coefficient
±0.005% of full scale/°C