*1 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value
between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.
Output Error Maximum Error at 25°C
(77°F)
±0.5% of full scale
Temperature Coefficient ±0.01% of full scale/°C
Repeatable after
Stabilization Time
±0.1% of full scale
Output voltage drop ±0.5% of full scale
Nonlinear ±0.2% of full scale
Output Ripple 1 LSB max.
Overshoot 0%
Total Error ±1% of full scale
Data Digital Resolution 11 bits + sign
Output Value of LSB ±9.8 mV
Data Type in Application
Program
-2,048 to +2,047*
1
Custom range up to
-32768 to +32767
Current Loop Open Not Detectable
Noise
Resistance
Maximum Temporary Deviation
during Electrical Noise Tests
±1% of full scale
Cable
Twisted-pair shielded cable is
recommended for improved noise immunity
Crosstalk No crosstalk because of 1channel output
Voltage Endurance
2500 VAC by photocoupler between
outputs, external power supply and
internal logic circuits
Selection of Analog Output Signal Type Using software programming
Calibration or Verification to Maintain
Rated Accuracy
Approximately 10 years
External Connection 11-pin terminal connector
EXM-AVO2HT
Analog Output Specifications Voltage Output