Manual
4
General Specifications
Electrical Specifications
DC Model AC Model
Power Supply
Input Voltage DC 24V AC 100 to 240 V
Rated Voltage DC 19.2 to 28.8 V AC 85 to 265 V
Allowable Voltage
Drop
10 ms (max.)
1 cycle or less (Voltage drop interval
must be 1s or more.)
Power Consumption
AGP-3500L
AGP-3500S
DC 24 V 2.08 A or less
(TYP 1.08 A)
AC 100 V 0.90 A or less
(TYP 0.45 A)
AC 240 V 0.45 A or less
(TYP 0.26 A)
AGP-3500T
AGP-3510T
AGP-3550T
AGP-3560T
DC 24 V 2.08 A or less
(TYP 1.22 A)
AC 100 V 0.90 A or less
(TYP 0.58 A)
AC 240 V 0.45 A or less
(TYP 0.29 A)
AGP-3600T
AGP-3650T
• When GP Rev.5 is NOT
marked
*1
DC 24 V 2.08 A or less
(TYP 1.30 A)
• When GP Rev.5 is marked
*1
DC 24 V 2.08 A or less
(TYP 1.0 A)
*1 For details on how to check the revision, See "About Revision" (page 1)
• When GP Rev.5 is NOT
marked
*1
AC 100 V 0.90 A or less
(TYP 0.55 A)
AC240 V 0.45A or less
(TYP 0.30A)
• When GP Rev.5 is marked
*1
AC 100 V 0.90 A or less
(TYP 0.40 A)
AC240 V 0.45A or less
(TYP 0.23A)
AGP-3600U
AGP-3650U
DC 24 V 2.08 A or less
(TYP 1.50 A)
AC 100 V 0.90 A or less
(TYP 0.55 A)
AC240 V 0.45A or less
(TYP 0.30A)
GP-3700
Series
50 W or less
AC 100 V 1.1 A or less
(TYP0.75 A)
AC 240 V 0.7 A or less
(TYP0.44 A)
In-Rush Current 30 A (max.) 60 A (max.)
Voltage Endurance
AC 1000 V 20 mA for
1 minute (between charging and
FG terminals)
AC 1500 V 20 mA for
1 minute (between charging and
FG terminals)
Insulation Resistance DC 500 V 10 MΩ (min.) (between charging and FG terminals)