User guide
FP3000 Series User Manual
4-30
4.3 FP-3650T Series
4.3.1 General Specifications
Electrical specifications
Environmental specifications
Items Specifications
Power Supply
Rated Voltage AC100 to 240V
Allowable Voltage AC85 to 265V
Rated Frequency 50 / 60Hz
Rated Frequency Range 40 to 72 Hz
Allowable Voltage Drop 1 cycle or less (Voltage Drop Interval is 1s or more)
Current Consumption
AC 100V 0.90A or less (TYP 0.55A)
AC 240V 0.45A or less (TYP 0.30A)
In-Rush Current 60A or less
Voltage Endurance AC1500V 20mA for 1 minute (between charging and FG terminals)
Insulation Resistance
DC500V 10MΩ or more (between charging and FG terminals)
Items Specifications
Physical
Surrounding Air Temperature
0 to 50°C
(The panel face should not incline more than 30 °C)
Storage Temperature -20 to +60°C
Ambient Operating Humidity
10 to 90%RH
(Wet bulb temperature: 39°C or less - no condensation.)
Ambient Storage Humidity
Air Purity (Dust) 0.1mg/m
3
or less (No electrically conductive dust is allowed)
Pollution Degree For use in Pollution Degree 2 environment
Corrosive gas Free of corrosive gas
Atomospherical pressure
Resistance
800 to 1114hPa (Under above sea level 2000m)
Mechanical
Vibration Resistance
IEC61131-2 compliant
5 to 9Hz Half amplitude 3.5mm
9 to 150Hz Constant acceleration 9.8m/s
2
X, Y, Z each direction 10 cycles (100 minutes)
Impact Resistance
IEC61131-2 compliant
(147m/s
2
, X, Y, Z each direction 3 times)
Electrical
Noise Immunity
(via noise simulator)
Noise Voltage: 1,500Vp-p
Pulse Duration: 1µs,
Rise Time: 1ns
Electrostatic Discharge
Immunity
6kV (EN61000-4-2 compliant)
Surge Resistance
Normal Mode: 1 kV
Common Mode: 2kV