Owner manual

FP-2500/FP-2600 Series User Manual
3-9
3.2 Wiring
3.2.3 Connecting the Power Supply
When supplying power to the FP unit, be sure
to separate the input/output and operation unit
lines, as shown.
To increase the noise resistance quality of the
power cable, be sure to twist each power wire
before attaching the Ring Terminal.
The power supply cable must not be bundled or
positioned close to main circuit lines (high
voltage, high current), or input/output signal lines.
Connect a lightning surge absorber, as shown in
the diagram, to deal with power surges.
To avoid excess noise, make the power cable as
short as possible.
Be sure to ground the
surge absorber (E1)
separately from the FP
unit (E2).
Select a surge absorber
that has a maximum
circuit voltage greater
than the power supply's
peak voltage.