Installation Sheet

PROFLO.COM 5
ELECTRICAL REQUIREMENTS AND INFORMATION
1. Whirlpool units require dedicated 20 Amp,120V service.
2. You must provide a receptacle with a 20-amp conguration.
3. See local codes for proper wire size. If not specied, use #12 Copper only wire.
The unit must be connected to a circuit interrupter (GFCI) provided by the installer. The (GFCI) breaker should be tested on a routine basis.
To test the (GFCI) breaker, push the test button. The GFCI should interrupt power. To restore power, push the RESET button. If the GFCI fails
to operate in this manner there is ground current owing, indicating the possibility of an electrical shock. Do not use the unit. Disconnect the
unit and have the problem corrected by a qualied service representative before using.
RISK OF ELECTRICAL SHOCK. All pumps and blowers must be connected
to a ground fault circuit interrupter (GFCI) protected outlets. Standard Line
Total Massage units can be operated on a single service. All heaters must be
connected to a ground fault circuit interrupter (GFCI) protected outlets, separate
from the pump and/or blower.
Electrical outlet must be mounted 4" (101mm) above the oor line and 12"
max (305mm) inside from the edge of the bathtub, or in accordance with local
building and electrical codes.
Risks of component over heat. Do not use electric extension cord to power
the unit. Operating the pump without enough water in bathtub can cause
permanent damage to the pump/motor.
If CFGI unit indicates a malfunction, per manufacturer’s instructions, turn OFF
power and do not attempt to use the bathtub until the source of the problem
has been identied and corrected.
WARNING
WARNING
TOTAL MASSAGE CIRCUIT WITH OPTIONAL HEATER
PUMP FLOW
CONTROLL VALV E
0.5 AMP
BACK OF 6 BTN CONTROL
PIGGY BLOWER
9.5 AMP
TMS - VARIABLE
CONTROL
TMS-P/TIMER
CONTROL
ON / OFF PUMP
9 AMP
OPTIONAL
120V, 60 HZ
20 AMP GFCI
120V / 20AMP
MALE PLUG
GFCI GFCI
ELECTRICAL
FEED
120V, 60 HZ
20 AMP GFCI
HEATER
AIR SPEED WAVE SPEEDJETS WAVE
WHIRLPOOL CIRCUIT WITH OPTIONAL HEATER
PUMP FLOW
CONTROLL VALV E
0.5 AMP
TMS-P/TIMER
CONTROL
ON / OFF PUMP
9 AMP
OPTIONAL
HEATER
120V, 60 HZ
20 AMP GFCI
120V / 20AMP
MALE PLUG
GFCI GFCI
ELECTRICAL
FEED
120V, 60 HZ
20 AMP GFCI
BACK OF 3 BUTTON CONTROL
AIR MASSAGE CIRCUIT
PIGGY BLOWER
9.25 AMP
TMS - VARIABLE
CONTROL
120V, 60 HZ
20 AMP GFCI
GFCI GFCI
ELECTRICAL
FEED
120V, 60 HZ
20 AMP GFCI
GFCI GFCI
ELECTRICAL
FEED
BACK OF 3 BUTTON CONTROL
120V, 60 HZ
20 AMP GFCI
GFCI GFCI
ELECTRICAL
FEED
120V, 60 HZ
9.25 AMP
HEATER
PIGGY BLOWER
9.5 AMP
AIR SWITCH
ON / OFF PUMP
9 AMP
AIR SWITCH
CONTROL BOX
CONTROL BOX
PIGGY BLOWER
9.5 AMP
PUMP / MOTOR
120V, 60 HZ
20 AMP GFCI
GFCI GFCI
ELECTRICAL
FEED
AIR SWITCH
AIR SWITCH
BRADENTON & PROVINCETOWN TOTAL MASSAGE
CIRCUIT WITH OPTIONAL HEATER
BRADENTON & PROVINCETOWN
AIR BATH CIRCUIT
BRADENTON & PROVINCETOWN WHIRLPOOL
WITH INSTALLED AIR SWITCH
POWER SPEED WAVE
POWER SPEED WAVE
PROFLO WHIRLPOOL
WITH INSTALLED AIR SWITCH