JAROL Assumes the promotion of energy-saving technology as its own task! 1. PREFACE Thanks for choosing JR6000 series frequency inverter! This manual introduces how to use the JR6000 frequency inverter correct.Before you use the frequency inverter , please read this manual carefully and know the safety precautions clearly NOTICE · In order to explain the detailed things , some of the pictures are the frequency inverter remove the shape.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products CONTENTS ....................................................................................................................................... 1 1. PREFACE PREFACE....................................................................................................................................... .........................................................................................................................................
JAROL Assumes the promotion of energy-saving technology as its own task! 5.1 KEYPAD DESCRIPTION......................................................................................................... 39 5.2 OPERATION PROCESS.......................................................................................................... 43 5.3 RUNNING STATE................................................................................................................... 45 5.4 SHORTCUT MENU........................
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 7.2 COMMUNICATION MODES................................................................................................... 106 7.3 PROTOCOL FORMAT........................................................................................................... 106 7.4 PROTOCOL FUNCTION........................................................................................................ 107 7.5 NOTE:................................................
JAROL Assumes the promotion of energy-saving technology as its own task! 1. SAFETY PRECAUTIONS WARNING:Points out potential danger which, if not avoided, may cause physical injury or death. Points out potential danger which, if not avoided, may ! CAUTION CAUTION:: result in mild or moderate physical injury and damage to the equipment. It’s also available to warns about unsafe operations. In some cases, even the content described in “Note” may also cause serious accidents.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products st the set screw of the equitment, especially the screws marked in RED. · Do not lo lost Caution ·Do not drop the lead wire stub or screw in the inverter.
JAROL Assumes the promotion of energy-saving technology as its own task! 1.1.5 Upon Power-on 1.1.5Upon Power-on: Caution · At power-on, the inverter will perform the security check of the external heavy-current circuit automatically. Thus, at this time please do not touch the terminals U, V and W, or the terminals of motor, otherwise there will be danger of electric shock! · The inverter is free from dielectric test because this test is performed prior to the delivery.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Danger · If parameter identification is required, due attention shall be paid to the danger of injury arising from the rotating motor. Otherwise accident may occur occur! · Do not change the factory settings at will. Otherwise it may damage the equipment! In Service 1.1.7 1.1.7In Service: Danger ·Do not touch the fan or discharge resistor to sense the temperature.
JAROL Assumes the promotion of energy-saving technology as its own task! there will be danger of electric shock! · be sure to conduct repair and maintenance after the charge LED indictor of the inverter is OFF. Otherwise, the residual charge on the capacitor may cause personal injury! · The inverter shall be repaired and maintained only by the qualifed person who has received professional training.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products when the inverter has no output. Otherwise the modules in the inverter may be damaged. 1.2.8 Use under voltage rather than rated voltage If the series inverter is used outside the allowable working voltage range as specifed in this manual, it is easy to damage the devices in the inverter. When necessary, use the corresponding step-up or step-down instruments to change the voltage. 1.2.
JAROL Assumes the promotion of energy-saving technology as its own task! 2. PRODUCT INFORMATION 2.1 Naming rule JR6000-15G/18P-4-1030 Series Shape Type Material Phase Type KW Not Defined 1. Series:Different Series,we have JR6 Series、JR7 Series 2. Material:0 means Module、1 means Transistor 3. Type:0 no meaning (follow the KW as G、P,G means universal type,P means fan and pump type)、 1 means woodworking special type 4. KW:Number means KW big or small,from 0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 2.2Nameplate 2.3 Frequency inverter series type Type Input V JR6000-0R7G-4-1010 Rated output KW (KW KW) Rated input current A) (A Rated output current A) (A Motor KW (KW KW) 0.75 3.4 2.5 0.75 1.5 5.0 3.7 1.5 2.2 5.8 5 2.2 4.0/5.5 10/15 9/13 4.0/5.
JAROL Assumes the promotion of energy-saving technology as its own task! ~+15% JR6000-5R5G/7R5P-4-1020 5.5/7.5 15/20 13/17 5.5/7.5 JR6000-7R5G/011P-4-1020 7.5/11.0 20/26 17/25 7.5/11.0 JR6000-011G/015P-4-1030 11.0/15.0 26/35 25/32 11.0/15.0 15.0/18.5 35/38 32/37 15.0/18.5 18.5/22.0 38/46 37/45 18.5/22.0 22.0/30.0 46/62 45/60 22.0/30.0 30.0/37.0 62/76 60/75 30.0/37.0 JR6000-037G/045P-4-1050 37.0/45.0 76/90 75/90 37.0/45.0 JR6000-045G/055P-4-1050 45.0/55.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Important function Product functions Frequency given way Frequency Range Multifunctions shortcut key 0.1-3600.0s Special function DC braking start frequency:0.00-400.00Hz;DC braking current: 0.0-150%;DC braking time:0.0-50.
JAROL Assumes the promotion of energy-saving technology as its own task! 2.5 Parts Description 1、0.4KW-15KW Plastic shape description Picture 2-1 0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Picture 2-2 18.5KW-55Kw part’s name 3. INSTALLATION 3.1 Install Environment 1、Temperature:-10℃~+50℃, if the temperature is above 40℃,please put your inverter in place well inventilized. 2、Humidity: 0%~95% without dew. 3、Away from corrosive gas ,liquid,oil mist or salt mist. 4、No dust or metal powder or debris. 5、No viberation and machinery shock. 6、No electromagnetion noise(such as welding machine). 3.
JAROL Assumes the promotion of energy-saving technology as its own task! and its adjacent objects in all directions. Figure 3-1 Installtion Distance 3.3 More than two inverters install If two inverters installed one onto the other,a guide plate is necessary Figure 3-2 Install More Than two Inverters 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Figure 3-4 1.5KW-15KW External Diemensions Figure 3-5 18.5KW-55KW External Diemensions NOTE:Install 18.
JAROL Assumes the promotion of energy-saving technology as its own task! Diemension 0.75~2.2 113.5 161.5 170 125 149 5 4~7.5 132 204 220.5 150 174 7 11~15 115 436.5 453 153 218.2 6 18.5~30 176 454.5 467 290 215 6.5 37~55 230 564.5 577 375 270 7 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 4.
JAROL Assumes the promotion of energy-saving technology as its own task! ●Only qualified electricians are allowed to operate on the safe running of the iverter. ●Never carry out any insulation or voltage withstand tests on the cables connecting with the inverter. ●Even if the inverter is stopped, dangerous voltage is present at the input power lines, DC circuit terminals and motor terminals.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Figure 4.1 Connection of peripheral devices.
JAROL Assumes the promotion of energy-saving technology as its own task! 4.2 Terminal Configuration 4.2.1 Main Circuit Terminals(AC 380V) Figure 4-2 Main Circuit Terminals(0.75KW~2.2KW) Figure 4-3 Main Circuit Terminals(4.0KW~7.5KW) Figure 4-4 Main Circuit Terminals(11KW~15KW) Figure 4-5 Main Circuit Terminals(18.5KW~30KW) Figure 4-6 Main Circuit Terminals(37KW~55KW) 4.2.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Terminal Symbol R、S、T Function Description Terminals of 3 phase AC input Spare terminals of external braking unit ( 380V up (+)、(-) 18.5kW) Spare terminals of external braking resistor,380V down (+)、PR 15kW P1、(+) Spare terminals of external DC reactor U、V、W Terminals of 3 phase AC output Terminal of ground 4.2.3 Main Circuit Standard Connect 0.75-15KW 18.
JAROL Assumes the promotion of energy-saving technology as its own task! 4.2.4 Wiring at input side of main circuit when fault occurs to the system, it is necessary to install a contactor at the input side to control Circuit breaker the ON-OFF of the main circuit power supply.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products following figure. • Please pay attention to safety prevention and 4.2.5 Wiring at inverter side of main circuit smooth DC reactor the heat releasing. ventilation when installing braking resistors because the temperature will rise for • The (+) and (-) terminal of the braking units JR6000 series inverters from 18.
JAROL Assumes the promotion of energy-saving technology as its own task! motor Do not connect electromagnetic switch or The output terminals of inverter U, V , W are electromagnetic contactor to output loop, the connected to motor input terminals U, V , and action of such components will cause over W. current or over voltage protection of inverter. When power is on, please check if motor is Much worse, it will damage inverter ’ s internal running forwardunder forward command, if components.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products grounding wire should be short with a thick diameter, and it is better to use multi-wires which have copper core (>3.5mm2). When multiple inverters need to be grounded, it is recommended to use command grounding wire for the avoidance of loop the ground wire. 4.3WiringControlCircuit terminal connect 4.3.
JAROL Assumes the promotion of energy-saving technology as its own task! 3.2 Control circuit terminals 4. 4.3 Figure 4-10 Control circuit terminals 3.3 Control circuit terminals explain 4. 4.3 Terminal Description ON-OFF signal input, optical coupling with PW and COM. S1~S7 Input voltage range: 9~30V Input impedance: 3.3kΩ High speed pulse or ON-OFF signal input, optical coupling with PW and COM.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products GND Common ground terminal of analog signal and +10V. GND must be isolated from COM. High speed pulse or open collector output terminal. The corresponding HDO common terminal is COM. Output frequency range: 0~50 kHz analog output terminals, of which AO1 can be selected to voltage output or AO1、AO2 current output by J3; AO2 can be selected to voltage output or current output by J4.
JAROL Assumes the promotion of energy-saving technology as its own task! 3.4 Multi Functionsinput and output terminal connect 4. 4.3 .
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products shortcircuit between PLC and COM terminal.
JAROL Assumes the promotion of energy-saving technology as its own task! NOTES:pick off the short circuit slice between +24Vand PLC terminal Use the inverter inside power +24Vand outside power’s multi functions output terminal connect mode: NOTES : Use this connect mode ,if have HDO terminal bad ,please confirm the out connect Diode polarity is right or wrong 4.3.
JiaXing Jarol Scientific Instrument Co.
JAROL Assumes the promotion of energy-saving technology as its own task! 4.4 Installation Guidline to EMC Compliance 4.4.1 General knowledge of EMC EMC is the abbreviation of electromagnetic compatibility, which means the device or system has the ability to work normally in the electromagnetic environment and will not generate any electromagnetic interference to other equipments. EMC includes two aspects: electromagnetic interference and electromagnetic immunity.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 4.4.2.2 Output voltage is high frequency PMW wave, which can increase the temperature rise and shorten the life of motor. And the leakage current will also increase, which can lead to the leakage protection device malfunction and generate strong electromagnetic interference to influence the reliability of other electric devices. 4.4.2.3 As an electromagnetic receiver, too strong external interference will cause malfunction and damage.
JAROL Assumes the promotion of energy-saving technology as its own task! Power supply wiring: the power should be separated supplied from electrical transformer. Normally it is 5 core wires, three of which are fire wires, one of which is the neutral wire, and one of which is the ground wire.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products control system should use common pole grounding, and different devices connected by same power cable should use series-wound grounding. 4.4.3.4 Leakage Current Leakage current includes line-to-line leakage current and over-ground leakage current. Its value depends on distributed capacitances and carrier frequency of inverter.
JAROL Assumes the promotion of energy-saving technology as its own task! EN61000-6-4: Electromagnetic Interference Detection on the industrial condition. EN61800-3: Comply with the electromagnetic radiation standard of EN61800-3 (The second environment). Can comply with the electromagnetic radiation standard of EN61000-6-3(residence) and standard of EN61000-6-4. 5.OPERATION KEYBOARD AND OPERATION 5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 5.1.1 Keypad schematic diagram Figure 5-1 Operation Keyboard 5.1.
JAROL Assumes the promotion of energy-saving technology as its own task! Key Name Program/Escape Data enter Key Function Description Enter or escape from the first level menu, Progressively enter menu and confirm parameters. Digital modify key Progressively increase data or function codes. Digital modify key Progressive decrease data or function codes. In parameter setting mode, press this button to select the bit Shift Key to be modified.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Determined by Function Code F7.03: 0: Display status switching 1: Jog operation 2: Switch between forward and reverse 3: Clear the UP/DOWN settings. 4: Quick debugging mode Shortcut Key + Pressing the RUN and STOP/RST at the same time can Combination Key achieve inverter coast to stop. 5.1.
JAROL Assumes the promotion of energy-saving technology as its own task! Unit indicator Description Extinguished: keypad control LOC/REM Flickering: terminal control Light on: communication control TRIP Extinguished: normal operation status Flickering: overload pre-warning status 2)Unit Indicator Light Description: Unit indicator Description Hz Frequency unit A Current unit V Voltage unit RPM Rotating speed unit % Percentage 3)Digital Display: Have 5 digit LED , which can display all kind
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products � 5.2 Operation Process This function code is not modifiable in running status, but modifiable in stop status. 5.2.1 Parameter setting 5.2.2 Fault reset Three levels of menu are: If fault occurs to the inverter, it will inform the � Function code group (first-level); related fault information.
JAROL Assumes the promotion of energy-saving technology as its own task! And then input following parameters according to parameter autotune has been finished. the actual motor parameters: coupled from Note: The motor should be dede-coupled F2.01: motor rated power. the load; otherwise, the motor parameters F2.02: motor rated frequency; obtained by autotuning may be incorrect. 5.2.4 Password setting F2.03: motor rated speed; F2.04: motor rated voltage; JR6000 series inverter provides password F2.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products status. Whether or not to display depends on setting the 5.3 Running State corresponding binary bit of F7.08. Press the 》 /SHIFT to scroll through the parameters in right 5.3.1 Power-on initialization order. Press DATA/ENT + QUICK/JOG to scroll Firstly the system initializes during the inverter through the parameters in left order. power-on, and LED displays “JAROL”. After the 5.3.
JAROL Assumes the promotion of energy-saving technology as its own task! In fault status, inverter will display parameters of STOP status besides parameters of fault status. Press the 》 /SHIFT to scroll through the parameters in right order . Press DATA/ENT + QUICK/JOG to to scroll through the parameters in left order. JR6000 series inverter offers a variety of fault information. For details, see inverter faults and their troubleshooting. 5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products accuracy, and quicker dynamic response, such as machine 6.DETAILED FUNCTION DESCRIPTION injection molding machine, centrifugal machine and wire-drawing machine, etc. One inverter only drives oine motor. 2. Torque control (sensorless vector control): It is F0 Group Basic Function suitable for the application with low accuracy torque control, such as wired-drawing. Function Name code F0.
JAROL Assumes the promotion of energy-saving technology as its own task! UP/DOWN The control commands of inverter include: start, setting stop, forward run, reverse run, jog, and fault reset and so on. The frequency can be set by “∧”, “∨” and 0: Keypad (LED extinguished); terminal UP/DOWN. This setting method have Both RUN and STOP/RST key are used for the highest and it cab be combined with setting running command control. If Multifunction key channel.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products When the factory setting is restored, the Note Note:When This is the lower limit of the output frequency of value of keypad and UP/DOWN will be cleared. the inverter. Function code F0.03 This parameter can be selected by function code Name Setting range F1.12. If the setting frequency is lower thanthe Maximum 10.00~400.00 Hz frequency upper limit, the inverter will run, stop or hibernate 【50.00Hz】 at the lower limit frequency.
JAROL Assumes the promotion of energy-saving technology as its own task! Select Frequency A command input channel and Pulse specification: pulse voltage range 15~30V, there are 8 main given frequency channels. and pulse frequency range 0.0~50.0 kHz. 100% of 0: Keypad: Please refer to description of F0.06 the setting inpluse corresponds to maximal Set the frequency by keypad through modifying frequency, while -100% corresponds with minus F0.06. maximal frequency.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 2:HDI priority. So stage 1~15 can be set when F0.07 is multi-stage speed setting. When B frequency command is the only frequency 6. PID control reference channel, its application is the same with The running mode is prodecure PID control A frequency command. For details, please refer to when selecting this parameter. It is e necessary to F0.07. set F9 group. The reference frequency is the Function result of PID adjustment.
JAROL Assumes the promotion of energy-saving technology as its own task! model】 code Frequency F0.10 Acceleration time is the time of accelerating from 0~3【0】 command 0Hz to maximum frequency (F0.03). Deceleration selection Setting time is the time of decelerating from maximum 0: Only frequency command source A is active. frequency (F0.03) to 0Hz. Please refer to following 1: Only frequency command source B is active. figure. 2: Both Frequency command source A and B are active.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 3rd group: F8.02, F8.03 4th group: F8.04, F8.05. Function selected by combination of multifunctional code Name Setting range 1.0~15.0kHz ON-OFF input terminals Function Name code The acceleration and deceleration time can be F0.14 Carrier frequency Setting range 【dependent on the motor type】 Running F0.13 direction 0~3【0】 selection 0: Runs at the default direction, the inverter runs in the forward direction.
JAROL Assumes the promotion of energy-saving technology as its own task! 75~630kW 6 1.0 AVR function is the output voltage automatic 2 adjustment function. When AVR is invalid, the The advantage of high carrier frequency: ideal output voltage will change with the intput voltage current waveform, little current harmonic wave (or DC bus voltage); when AVR is valid, the output and motor noise.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products before performing autotuning. Otherwise it may rotation autotuning except step c. Function cause over-current and over-voltage fault during Name code autotuning. Set F0.16 to be 1 then press the DATA/ENT, Setting range Restore F0.17 LED will display “-TUN-” and flickers. During 0~2【0】 parameters “-TUN-” is flickering, press the PRG/ESC to exit 0: No action autotuning.
JAROL Assumes the promotion of energy-saving technology as its own task! F1.03 and F1.04. It is suitable for the motor which reference frequency is less than starting frequency, have small inertia load and may reverse rotation the inverter will be at stand-by status. The when start. indicator of RUN/TUNE lights on, inverter has no 2: Speed tracking and start: Inverter detects the output.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Deceleration frequency of mode DC braking Waiting time The frequency changing method during the F1.08 running and starting of the inverter. Output frequency will increase or decrease with F1.09 fixed acceleration or deceleration time. 1: Reserved code F1.06 before DC 0.0~50.0s 【0.0s】 braking 0: Linear Function 【0.00Hz】 F1.10 Name Setting range Stop mode 0~1【0】 DC braking 0.0~150.0% current 【0.0%】 DC braking 0.0~50.
JAROL Assumes the promotion of energy-saving technology as its own task! is. DC braking time: The time used to perform DC braking. If the time is 0, the DC braking will be invalid. Figure 6.4 FWD/REV dead time diagram. Function Figure 6.3 DC braking diagram. Function code F1.11 Name Setting range Dead time of 0.0~3600.0s FWD/REV 【0.0s】 code Name Setting range Action when running frequency is F1.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 1: Stop: This parameter is used to prevent motor 0: Disabled: Inverter will not automatically restart running at low speed for a long time. when power on again until run command takes 2: Stand-by: Inverter will Coast to stop when the effect. running frequency is less than the lower frequency 1: Enabled: When inverter is running, after limit.
JAROL Assumes the promotion of energy-saving technology as its own task! source is terminal control. G/P unification, which means the power of the If F1.15 is set to be 0, when power on, inverter will motor used in G type is lower than the power of not start even if FWD/REV terminal is active, until the motor used in P type for one gear. FWD/REV terminal disabled and enabled again. The factory setting of the inverter is G model. If P If F1.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function Name code Setting range F2.08 Motor leakage 0.1~6553.5mH 【Depend on inductance model】 model】 Note: In order to achieve superior F2.09 performance, please set these parameters Motor mutual The inverter F2.10 provides parameters 【Depend on inductance according to motor nameplate, and then perform autotuning. 0.1~6553.5mH Current without model】 0.1~6553.5A 【Depend on load model】 autotune.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F3.01 Name Setting range ASR integral 0.01~10.00s time Ki1 【0.50s】 ASR switching F3.02 lower 0.00~F3.05 【5.00Hz】 Figure 6-6 freqeuncy ASR F3.03 proportional 0~100 the proportion gain Kp is increased; 【15】 However, if Kp is too large, the system tends to gain Kp2 F3.04 ASR integral 0.01~10.00s time Ki2 【1.00s】 ASR switching F3.05 lower PI parameter diagram.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products compensation 【100%】 1:AI1 rate of VC 2:AI2 The parameter is used to adjust the slip frequency 3: HDI of vector control and improve the precision of 4:Multi-step speed speed control. Properly adjust this parameter can 5:Communication effectively restrain the static speed bias. 1~5: Torque control is valid, which defines the Function code F3.07 torque setting source.
JAROL Assumes the promotion of energy-saving technology as its own task! output frequency of the inverter is limited, the 5:Communication output torque will be different from the set torque. Note: Note: maximum frequency. � Corresponds to F4 Group V/F Control terminals. Valid when F0.00=0. Function 1~5: 100% corresponding to twice of code rated current of inverter.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products When the torque boost is set to 0.0%, the inverter is in the automatic torque boost state. Cut-off point of torque boost:the torque boost is valid under this point, and the torque boost is invalid when exceeding this set frequency. Figure 6-7 Function code V/F Curve Name Setting range 0.0~10.0% F4.01 F4.02 Torque boost 【0.0%】 Torque boost 0.0~50.0% cut-off 【20.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Setting range V/F F4.05~F2.02 Function frequency3 【0.00Hz】 code Figure 6.9 V/F curve setting diagram. F4.07 Name 0.0~100.0% F4.08 V/F voltage3 V/F Slip 【0.0%】 F4.09 Setting range 0.0~200% compensation 【0.0%】 limit F4.03~F4.08 are used to set the user-defined V/F curve. The value should be set according to the The slip compensation function calculates the load characteristic of motor.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products F4.11~F4.12 are only valid in the V/F control 0: Disabled mode, When set F4.11 and F4.12 to be 0, the 1: Enabled restraining oscillation is invalid. While set the While there is a light or empty load such as pumps values to be 1~3 will have the effect of restraining or fans, it will reduce the inverter output voltage oscillation.When the running frequency is lower and save energy through detecting the load than F4.13, F4.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name S3 terminal F5.03 Setting range F5.04 Jog forward 5 Jog reverse 0~39【7】 function S4 terminal 4 6 0~39【0】 function 7 Function code Name Setting range S5 terminal 0~39【0】 F5.05 function 8 S6 terminal 0~39【0】 F5.06 function S7 terminal 0~39【0】 F5.07 function 9 HDI terminal 0~39【0】 F5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products combination of these two terminals: reference frequency through external terminals. UP is the increasing command, DOWN is the Terminal Terminal ACC ACC//DEC decreasing command, and the Clear UP/DOWN is used to restore to the reference frequency given 2 1 OFF OFF by the frequenxy command channel.
JAROL Assumes the promotion of energy-saving technology as its own task! pause. UP/DOWN setting is invalid but will not be 25:Pause PID cleared. PID adjustment will be paused and inverter UP/DOWN value before will be valid again. When this terminal is disabled, 33~39:Reserved keeps output frequency unchanged. 26:Pause traverse operation Function Name code Inverter keeps output frequency unchanged. If this terminal is disabled, inverter will continue F5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products ON OFF SB2:Stop button FWD OFF ON REV ON ON Maintenance Sin set for 3 NO. function3-wires running contry multi-functions input terminal . 3:3-wire control mode 2 Figure 6.9 2-wire control mode 1. 1 : 2-wire control mode 2: START/STOP SB1: Forward run button command is determined by FWD terminal. Run SB2: Stop button (NC) direction is determined by REV terminal.
JAROL Assumes the promotion of energy-saving technology as its own task! � Stop command from serial use function Some communication. communication.S see F7.04 These parameters relationship determine between analog the input voltage and the corresponding setting value. When the analog input voltage Figure 6-13 exceeds the range between lower limit Relationship between AI and corresponding setting.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function Name code Function Setting range code setting F5.26 AI2 filter time 0.00~10.00s constant 【0.10s】 F5.21 Setting range HDI lower 0.00~50.00kHz limit 【0.00kHz】 terminal in JR6000 Function code limit -100.0~100.0% corresponding 【0.0%】 F6.00 series inverters. Name HDO Setting range 0~1【0】 select 0: High-speed pulse output: The maximum pulse HDI upper 0.00~50.00kHz frequency is 50.0 kHz.
JAROL Assumes the promotion of energy-saving technology as its own task! 8 : Preset count value reached , Please refer to HDO ON-OFF F6.01 output 0~20【1】 description of F8.18. 9:Specified count value reached,Please refer to selection Relay 1 output F6.02 description of F8.19. 0~20【4】 10:overload pre-warming of inverter,Please refer selection to description of Fb.04~Fb.06 Relay 2 output F6.03 selection 11:Simple PLC step completed 0~20【0】 , After simple PLC completes one step, inverter (4.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products code AO1 function F6.04 F6.05 AO2 function Output 0~1.
JAROL Assumes the promotion of energy-saving technology as its own task! Function Name code Setting range output 0.0~100.0% F6.09 AO1 upper limit 【100.0%】 AO1 upper limit 0.00~10.00V F6.10 corresponding Figure 6.14 Relationship between AO and 【10.00V】 corresponding setting. output These parameters determine the relationship Function between analog output voltage/current and the code corresponding output value. When the analog F6.11 Name 0.0~100.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F7.00 is set to be 00000, user’s password set Name Setting range before will be cleared and the password protection corresponding 【0.00kHz】 function will be disabled. After the password has been set and becomes output F6.17 HDO upper limit 0.0~100.0% valid, the user can not access menu if the user’s 【100.0%】 password is not correct. Only when a correct HDO upper limit F6.
JAROL Assumes the promotion of energy-saving technology as its own task! selection � The RESET function of STOP/RST is QUICK/JOG is a multifunctional key, whose always valid. Function function can be defined by the value Name code 0. Display status switching 1: Jog: Press QUICK/JOG, the inverter will jog. Setting range Keypad 2: FWD/REV switching: Press QUICK/JOG , the display F7.05 0~3【0】 selection running direction of inverter will reverse. It is only valid if F0.03 is set to be 0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products status display 【0x07FF】 selection 1 voltage voltage When the JR6000 series frequency inverter example inputposition display 3,means S1 ,S2 parameters in right order . Press DATA/ENT + always close,other terminal break,the detailed QUICK/JOG to scroll through these parameters in information please check F7.23 and F7.24 left order. Function The display content corresponding to each bit of Name code F7.
JAROL Assumes the promotion of energy-saving technology as its own task! % BIT3 d d d d d BIT9 BIT8 BIT7 BIT6 BIT5 PLC HDI BIT2 BIT1 BIT0 value Motor overload HDI AI2 e set AI1 BIT4 PID PID % Function Name code feedbac AI2 AI1 BIT1 BIT0 preset k Setting range Stop status 0~0xFFFF display selection 【0x07FF】 F7.08 BIT3 BIT2 output Input Set DC BUS frequen terminal terminal 7.08 determines the display parameters in stop cy status. The setting method is similar with F.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 【1.0%】 line speed protection point of different model may be This parameter is used to calculate the line speed different. based on actual mechanical speed. The formula is IGBT as below: temperature of IGBT module. Overheat protection module temperature: Indicates the Line speed = actual mechanical speed *F7.10 point of different model may be different.
JAROL Assumes the promotion of energy-saving technology as its own task! current fault F7.21 F7.22 F7.23 terminal status at current fault. Output current This value is displayed as decimal. The meaning at current fault of each bit is as below:: DC bus BIT3 BIT2 BIT1 BIT0 voltage at Reserved RO2 RO1 HDO current fault 1 indicates corresponding output terminal is ON, Input terminal while 0 indicates OFF. Notice: This value is status at displayed as decimal.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 0.1~3600.0s F8.04 F8.05 Acceleration time 3 Deceleration model】 Function 0.1~3600.0s code 【Depend on time 3 and the above model】 Name Setting range Skip 0.00~F0.03 Frequency 1 【0.00Hz】 F8.09 model】 ACC/DEC time can be seleted among F0.11, F0.12 time 【Depend on three Skip 0.00~F0.03 Frequency 2 【0.00Hz】 F8.10 groups. Their meanings are the same. Please refer to the Skip relative instructions of F0.11 and F0.
JAROL Assumes the promotion of energy-saving technology as its own task! during acceleration and deceleration frequency as its center. The route of the running are smooth without skip. frequency is illustrated as below, of which the traverse is set by F08.12 and when F08.12 is set as 0, the traverse is 0 with no function. Figure6-16 Function code Skip frequency diagram. Name Figure 6.17 Traverse operation diagram. Setting range Traverse range:The traverse running is limited by F8.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F8.16 F8.17 count value (F8.18), it will output an ON-OFF Name Setting range signal. Inverter will clear the counter and restart counting. Auto reset 0~3【0】 If function of output terminal is set as specified times Reset interval 0.1~100.0s count reached, when the count value reaches 【1.0s】 specified count value (F8.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F8.20 Name Setting range Preset running 0~65535h time 【65535h】 Pre-set running time of the inverter. When the accumulative running time achieves the set time, the multi-function digital output terminals will output the signal of “running time arrival”. Function code Name Figure 6-19 FDT level and lag diagram. Setting range Function F8.21 FDT level F8.22 FDT lag 0.00~F0.03 Name code 【50.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products between load and output frequency is in the following figure. Figure 6.20 Frequency arriving detection diagram. Function code F8.24 Name Droop control Setting range 0.00~10.00Hz Figure 6.21 Droop control diagram. 【0.00Hz】 Function When several motors drive the same load, each code motor's load is different because of the difference of motor's rated speed. The load of different F8.
JAROL Assumes the promotion of energy-saving technology as its own task! � � Function Factory setting is 130% if rated voltage of inverter is 380V. code 5 is corresponding to The value of F8.2 8.25 F8.28 the DC bus voltage at rated input code PWM 0~2【0】 Noise in higher frequency is high Name 1:PWM as 2,noise is so lower when motor Setting range working under this mode,but temperature rise Cooling fan F8.26 Setting range 0:PWM as 1,Noise in lower frequency is low, voltage.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products are percentage value. � 100% of preset value is corresponding to 100% of feedback value. Preset source and feedback source � Figure 6-22 Function PID control diagarm Name code must not be same, otherwise PID will be malfunction. Setting range Function PID preset F9.00 source Name Setting range Keypad PID 0.0~100.0% preset 【0.0%】 code 0~5【0】 F9.01 selection 0: Keypad (F9.01) Set the parameter when F9.00=0.
JAROL Assumes the promotion of energy-saving technology as its own task! Function 4: Communication code This parameter is used to select PID feedback Name 【0.10s】 source. The given channel and the feedback F9.06 channel can not coincide, otherwise, PID can not control effectively effectively.. Function code F9.03 Setting range Name Differential 0.00~10.00s time (Td) 【0.10s】 Optimize the responsiveness by adjusting these parameters while driving an actual load.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Reducing long-cycle oscillation diagram. time and lengthen the integral time. � Reducing short-cycle oscillation If the oscillation cycle is short and oscillation occurs with a cycle approximately the same as the differential time setting, it means that the differential operation is strong. The oscillation will be reduced as the differential time is shortened. Reducing overshooting diagram.
JAROL Assumes the promotion of energy-saving technology as its own task! Sampling cycle T refers to the sampling cycle of When feedback value. The PI regulator calculates once continuously for the period determined by F9.10, in each sampling cycle. The bigger the sampling the inverter will alarm feedback lost failure (PIDE). cycle is, the slower the response is. Note: 100% of F9.09 is the same as 100% of Bias limit defines the maximum bias between the F9.01. feedback and the preset.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products mode 0: Stop after one PLC record the running stage and frequency when cycle: Inverter power loss. stops Function automatically as soon as it completes one cycle, code and it needs run command to start again. 1: Hold last frequency after one cycle: Inverter FA.02 holds frequency and direction of last step after one cycle. FA.03 2: Circular run: Inverter continues to run cycle by cycle until receive a stop command. FA.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code FA.12 Name Setting range time 【0.0s】 Multi-step -100.0~100.0% speed 5 【0.0%】 5th running 0.0~6553.5s time 【0.0s】 Multi-step -100.0~100.0% speed 6 【0.0%】 6th running 0.0~6553.5s Function code FA.22 FA.14 FA.15 FA.16 FA.17 FA.18 FA.19 FA.20 FA.21 time 【0.0s】 Multi-step -100.0~100.0% speed 7 【0.0%】 7th running 0.0~6553.5s time 【0.0s】 Multi-step -100.0~100.0% speed 8 【0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function JR6000 series inverters can set 16 stages speed, Name code FA.33 Setting range selected by the combination of multi-stage speed 15 【0.0%】 15th Step running time 0.0~6553.5s terminals S1, S2, S3, S4, corresponding to the speed 0 to speed 15. 【0.0s】 When S1=S2=S3=S4=OFF, the frequency input 100.0% of the frequency setting corresponds to manner is selected via code F0.07 or F0.08. when the Max. Frequency. (F0.
JAROL Assumes the promotion of energy-saving technology as its own task! ACC/DEC 1 ACC/DEC 2 ACC/DEC 3 S2 OFFOFF ON ON OFFOFF ON ON ACC/DEC 0 S1 OFF ON OFF ON OFF ON OFF ON BIT11 BIT10 5 00 01 10 11 BIT3 BIT12 6 00 01 10 11 BIT15 BIT14 7 00 01 10 11 Binary Digit step S3 OFFOFFOFFOFF ON ON ON ON S4 ON ON ON ON ON ON ON ON stage 8 9 10 Function 11 12 13 14 15 Name code Setting range PLC FA.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products BIT4 10 00 01 10 11 interrupted time automatically. For details, please BIT7 BIT6 11 00 01 10 11 refer to following figure.
JAROL Assumes the promotion of energy-saving technology as its own task! Function Function code reduce the motor overload protection threshold to prevent normal motor from overheat. Name Setting range 1: Common motor (with low speed compensation). As the cooling effect of the common motor is Input Fb.00 Fb.01 phase-failure weakened at low speed, the corresponding 0~1【1】 protection electronic heating protection is adjusted.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products of trip-free 【0.00Hz】 100% of Fb.04 corresponds to the standard bus voltage. If Fb.05 is set to be 0, the trip-free function is invalid.Trip-free function enables the inverter to perform low-voltage compensation when DC bus Figure 6.31 Motor overload protection curve. voltage drops below Fb.04.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Over-voltage Fb.07 stall protection Setting range 110~150% 【120%】 point During deceleration, the motor’s decelerating rate may be lower than that of inverter’s output frequency due to the load inertia. At this time, the Figure 6.28 Over-voltage stall function. motor will feed the energy back to the inverter, resulting in rise of DC bus voltage rise.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products � Auto current Fb.10 limiting 0~1【0】 During auto current limiting process, the inverter inverter’’s output frequency may selection change; therefore, it is recommended not to enable the function when inverter 0: Enabled needs to output stable frequency 1: Disabled when constant speed � Therefore the inverter will not trip due to surge During auto current limiting process, if over-current.
JAROL Assumes the promotion of energy-saving technology as its own task! trip due to surge over-current. This function is Function especially useful for the applications with big load code inertia or step change of load. Name Setting range Selection of Fb.08 is a percentage of the inverter’s rated Fb.11 overtorque current. Fb.09 defines the decrease rate of output 0~4【1】 (OL3) frequency when this function is active. If Fb.08 is 0:No detection too small, overload fault may occur.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Fb.13 Detection time 0.1~60.0s When the master is writing the frame, the cof overtorque 【0.1s】 communication address of the slave is set to 0, the address is the communication address. All slaves on the MODBUS fieldbus can receive the frame, but the salve doesn’t answer. The communication of the drive is unique in the communication net. This is the fundamental for Figure 6.30 Overtorque control function.
JAROL Assumes the promotion of energy-saving technology as its own task! 5:38400bps serial communication protocol. Function This parameter can set the data transmission rate code during serial communication. The baud rate between the upper monitor and the Name Communicatio FC.03 inverter must be the same. Otherwise, the Setting range 0~200ms【5ms】 n delay time communication is not applied.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products code exceeds the communication overtime, the system will report “communication faults” (CE). Response FC.06 Generally, set it as invalid; set the parameter in the continuous communication to monitor the Unit’s place of LED communication state. 0: Response to writing Function code Name 1: No response to writing Setting range Ten’s place of LED Communicati FC.
JAROL Assumes the promotion of energy-saving technology as its own task! 7. COMMUNICATION PROTOCOL 7.1 Interfaces RS485: asynchronous, half-duplex. Default: 8-E-1, 19200bps. See Group PC parameter settings. 7.2 Communication Modes 7.2.1 The protocol is Modbus protocol. Besides the common register Read/Write operation, it is supplemented with commands of parameters management. 7.2.2 The drive is a slave in the network. It communicates in ‘point to point’ master-slave mode.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 7.3 Protocol Format Modbus protocol supports both RTU. The frame format is illustrated as follows: Modbus adopts “Big Endian” representation for data frame. This means that when a numerical quantity larger than a byte is transmitted, the most significant byte is sent first. RTU mode In RTU mode, the Modbus minimum idle time between frames should be no less than 3.5 bytes. The checksum adopts CRC-16 method.
JAROL Assumes the promotion of energy-saving technology as its own task! 7.4 Protocol function Different respond delay can be set through drive’s parameters to adapt to different needs. For RTU mode, the respond delay should be no less than 3.5 bytes interval. The main function of Modbus is to read and write parameters.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products eter Param Parame R/W Address Meaning of value Description Feature 0003H: Standby 0004H: Fault 0005H: Status of inverter POFF Communication Setting Range (-10000~10000) Note: the communication setting is the percentage of the relative value (-100.00%~100.00%). If it is set as 2000H W/R frequency source, the value is the percentage of the maximum frequency.
JAROL Assumes the promotion of energy-saving technology as its own task! eter Param Parame R/W Address Meaning of value Description Feature (0~Fmax) Status parameters 3000H Output frequency R 3001H Reference frequency R 3002H DC Bus voltage R 3003H Output voltage R 3004H Output current R 3005H Rotation speed R 3006H Output power R 3007H Output torque R 3008H PID preset value R 3009H PID feedback value R 300AH Input terminal status R 300BH Output terminal status.
JiaXing Jarol Scientific Instrument Co.
JAROL Assumes the promotion of energy-saving technology as its own task! eter Param Parame R/W Address Meaning of value Description Feature 0X00H: No fault 0X01H: SC1 0X02H: SC2 0X03H: SC3 0X04H: OC1 0X05H: OC2 0X06H: OC3 0X07H: OV1 0X08H: OV2 Inveter fault info 0X09H: OV3 5000H address R 0x0A: UV 0x0B: OL1 0x0C:OL2 0x0D: IPI 0x0E: SPO 0x0F: OH1 0x10: OH2 0x11: EF 0x12: CE 0x13: ItE 113
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products eter Param Parame R/W Address Meaning of value Description Feature 0x14: tE 0x15: EEP Inveter fault info 0x16:PIDE 5000H address R 0x17: bE 0x18: END 0x19: OL3 The above shows the format of the frame. Now we will introduce the Modbus command and data structure in details, which is called protocol data unit for simplicity. Also MSB stands for the most significant byte and LSB stands for the least significant byte for the same reason.
JAROL Assumes the promotion of energy-saving technology as its own task! Returned byte number 2 Content 2* Read number 2* Read number If the operation fails, the inverter will reply a message formed by failure command and error code. The failure command is (Command+0x80). The error code indicates the reason of the error; see the table below. Value Name Mean The command from master can not be executed.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Value Name allowed. Mean 1 The data to write exceed the range of according parameter 2 The parameter should not be modified now. 3 The terminal has already been used. When password protection take effect and user does not unlock it, 13H System locked write/read the function parameter will return this error.
JAROL Assumes the promotion of energy-saving technology as its own task! discarded. 7.5.2 Be cautious to modify the parameters of PC group through communication, otherwise may cause the communication interrupted. 7.5.3 In the same frame, if the span between two .near bytes more than 1.5 bytes interval, the behind bytes will be assumed as the start of next message so that communication will failure. 7.6 CRC Check For higher speed, CRC-16 uses tables. The following are C language source code for CRC-16.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products 7.7 Example RTU mode, read 2 data from 0004H The request command is: START T1-T2-T3-T4 (transmission time of 3.5 bytes) Node address 01H Command 03H High byte of start address 00H Low byte of start address 04H High byte of data number 00H Low byte of data number 02H Low byte of CRC 85H High byte of CRC CAH END T1-T2-T3-T4 (transmission time of 3.5 bytes) START T1-T2-T3-T4 (transmission time of 3.
JAROL Assumes the promotion of energy-saving technology as its own task! Low byte of 0005H 00H Low byte of CRC 43H High byte of CRC 07H END T1-T2-T3-T4 (transmission time of 3.5 bytes) 4H, slave node address 03 RTU mode, write 5000(1388H) into address 000 0004 The request command is: START T1-T2-T3-T4 (transmission time of 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products The reply command is: START T1-T2-T3-T4 (transmission time of 3.5 bytes) Node address 03H Command 06H High byte of data address 00H Low byte of data address 04H High byte of write content 13H Low byte of write content 88H Low byte of CRC C4H High byte of CRC BFH END T1-T2-T3-T4 (transmission time of 3.
JAROL Assumes the promotion of energy-saving technology as its own task! 8. TROUBLE SHOOTING ult and Trouble shooting 8.1 Fa Fault Fault Code Fault Type SC1 IGBT Ph-U fault SC2 IGBT Ph-V fault Reason Solution 1. Acc time is too short. 1. Increase Acc time. 2. IGBT module fault. 2. Ask for support. 3. Malfunction caused by 3. Inspect external equipment and SC3 IGBT Ph-W fault interference. eliminate interference. 4.Grounding is not properly. 1. Acc time is too short.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Fault Code Fault Type Reason Solution too low. 3. Select bigger capacity inverter. 3.The power of the inverter is too low. 1. Over-voltage when The input voltage is abnormal 1 Check the input power 2. Restart the running motor 2.Avoid restart-up after stopping OV1 acceleration after sudden power loss. Over-voltage when 1. Dec time is too short. 1.Increase the Dec time 2.The inertia of the load is big. 2. 3.
JAROL Assumes the promotion of energy-saving technology as its own task! Fault Code Fault Type Reason Solution current is incorrect. motor 3. The motor stall or load 3. Check the load and adjust the transients is too strong. torque lift 4.The power of the motor is 4. Select a proper motor. too big. 1. Increase the ACC time OL2 Inverter overload 1. The acceleration is too fast 2. Avoid the restarting after 2. Reset the rotating motor stopping. 3. The voltage of the power 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Fault Code Fault Type Reason Solution 1.Sudden overcurrent of the inverter Rectify IGBT OH1 2.There is direct or indirect overheat OH2 short circuit between output 3 1. phase solution Refer to the 3.Air duct jam or fan damage 2. Redistribute 4.Ambient temperature is too 3. Dredge the wind channel or high. change the fan 5.The wiring of the control 4. Low the ambient temperature panel or plug-ins are loose 5.
JAROL Assumes the promotion of energy-saving technology as its own task! Fault Code Fault Type fault Reason Solution incorrect. 2. Press STOP/RST to reset and 2.Communication fault ask for help 3.The communication is off for 3. a long time. connection distribution Check the communication 1. The connection of the control board is not good Assistant power is bad Current detection 2. Assistant power 1. Check and reconnect is 2. Ask for service ItE fault damaged 3. Hoare 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Fault Code Fault Type Reason Solution and the standard parameter is the parameters huge 4. Autotune overtime 1. Error of controlling the write 1.Press STOP/RST to reset EEP EEPROM fault and read of the parameters 2. Ask for service 2. Damage to EEPROM 1. PID feedback offline PIDE PID feedback fault 2. PID feedback 1.Check the PID feedback signal source disappear wires 2.Check PID feedback source 1.
JAROL Assumes the promotion of energy-saving technology as its own task! Fault Code Fault Type Reason Solution 4. Select an inverter with bigger power 5. Adjust Fb.11 to a proper value 8.2 Common Faults and Solutions Inverter may have following faults or malfunctions during operation, please refer to the following solutions. No display after power on: � Inspect whether the voltage of power supply is the same as the inverter rated voltage or not with multi-meter.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products � Inspect whether ground fault exists. If yes, solve it. � If trip happens occasionally and the distance between motor and inverter is too far, it is recommended to install output AC reactor.
JAROL Assumes the promotion of energy-saving technology as its own task! 9. MAINTENANCE WARNING ● Maintenance must be performed according to designated maintenance methods. ● Maintenance Maintenance,, inspection and replacement of parts must be performed only by rson certified pe person rson.. ● After turning off the main circuit power supply, wait for 10 minutes before maintenance or inspection. ● DO NOT directly touch components or devices of PCB board board..
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products inverter. Ensure the voltage and frequency of the power supply is in the allowed Input power supply range. The motor Ensure there is no abnormal vibration, heating noise and phase loss. 9.2 Periodic Maintenance Customer should check the inverter every 6 months according to the actual environment. Checking item Content Screws of the Cherck if the screw is loose Method Tjghten up external terminals PCB board or not.
JAROL Assumes the promotion of energy-saving technology as its own task! 9.4 Guarantee There is a 18months Warranty Period for your JR6000series inverter started from the date of purchase. 10.Specifications of Breaker Breaker,, Cable Cable,, ontactor and Reactor 10.1 Brake Resistor Specification Brake torque% Motor G 750 125 0.75 260 400 125 1.5 JR6000-2R2G-4-1010 260 250 125 2.2 JR6000-004G/5R5P-4-1020 390 150 125 4 5.5 JR6000-5R5G/7R5P-4-1020 500 100 125 5.5 7.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products JR6000-030G/037P-4-1040 6000 20 125 30 37 JR6000-037G/045P-4-1050 9600 16 125 37 45 JR6000-045G/055P-4-1050 9600 14 125 45 55 JR6000-055G/075P-4-1050 12000 10 125 55 75 NOTICE: Select the resistance value and frequency from our company. 1、Select We don 2、We don’’t bear any responsibility of inverter damage if braking resistance and chip used is not from our company.
JAROL Assumes the promotion of energy-saving technology as its own task! JR6000-022G/030P-4-1040 100 16 80 JR6000-030G/037P-4-1040 125 25 95 JR6000-037G/045P-4-1050 160 25 120 JR6000-045G/055P-4-1050 200 35 135 JR6000-055G/075P-4-1050 200 35 170 10.3 Specifications of input/output AC reactor and DC reactor Input AC reactor Type Output AC reactor DC reactor Curren t(A) Inducta nce (mH) curren t(A) Inductan ce(uH) Current (A) Inductan ce(mH) JR6000-1R5G-4-1010 5 3.8 5 3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products JR6000-045G/055P-4-1050 120 0.13 120 0.023 95 0.54 JR6000-055G/075P-4-1050 150 0.10 150 0.019 115 0.45 11. LIST OF FUNCTION PARAMETERS The function parameters of JR6000 series inverters have been divided into 16 groups F0~FE) according to the function. Each function group contains certain function codes applying 3-class menus. For example, “F8.
JAROL Assumes the promotion of energy-saving technology as its own task! and the modifying conditions),below is the instruction: “○”: means the set value of the parameter can be modified on stop and running state; “◎”: means the set value of the parameter can not be modified on the running state; “●”: means the value of the parameter is the real detection value which can not be modified.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Setting Description Factory mod NO. range setting ify 0~2 0 ◎ 0. 0~2 0 ◎ 1. 0~3 0 ○ 2. F0 Group Basic function F0Group 0: F0.00 V/F control Control 1: Sensorless vector control model 2: Torque control (sensorless vector control) 0: Run F0.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F0.03 Name Maximum Description F0.04 frequency limit Lower F0.05 frequency range Factory mod NO. setting ify 50.00Hz ◎ 3. 50.00Hz ○ 4. 0.00~F0.04 0.00Hz ○ 5. 0.00~F0.03 50.00Hz ○ 6. 0~7 0 ○ 7. 10.00~400.0 10.00~400.00Hz frequency Upper Setting 0 F0.05~F0.03(the Maximum F0.05~F0.0 frequency) 3 0.00~F0.04(Lower frequency limit) limit Keypad F0.06 reference frequency 0.00~F0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting Factory mod NO. range setting ify 0~2 0 ○ 8. 0~1 0 ○ 9. 0~3 0 ○ 10. ○ 11. ○ 12. ◎ 13. communication Frequency B 0:AI1 F0.08 command 1:AI2 source 2:HDI Scale of F0.09 frequency B command Frequency F0.10 command selection 0: Maximum frequency 1: Frequency A command 0: A 1: B 2: A+B 3: Max(A and B) Acceleration F0.11 time 0 Depend 0.1~3600.0s 0.1~3600.0 0.1~3600.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F0.14 Name Carrier Description 1.0~15.0kHz Setting range 1.0~15.0 frequency Factory mod setting Depend ify NO. ○ 14. on model 0:Invalid F0.15 AVR function 1:Valid all the time 0~2 1 ○ 15. 0~2 0 ◎ 16. 0~2 0 ◎ 17. 0~2 0 ◎ 18. 0.00~10.00 0.00Hz ◎ 19. 0.0~50.0 0.0s ◎ 20. 2:Only valid in deceleration Motor F0.16 1: Rotation autotuning autotuning 2: Static autotuning Restore F0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting Factory mod NO. range setting ify 0.0~150.0% 0.0~150.0 0.0% ◎ 21. 0.0~50.0s 0.0~50.0 0.0s ◎ 22. 0~1 0 ◎ 23. 0~1 0 ○ 24. 0.00~F0.03 0.00Hz ○ 25. 0.0~50.0 0.0s ○ 26. frequency DC Braking F1.03 current before start DC Braking F1.04 time before start Acceleration F1.05 / 0: Linear Deceleration 1: reserved mode F1.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting Factory mod NO. range setting ify 0.0~150.0% 0.0~150.0 0.0% ○ 27. 0.0~50.0s 0.0~50.0 0.0s ○ 28. 0.0~3600.0 0.0s ○ 29. 0~2 0 ◎ 30. before DC braking F1.09 DC braking current F1.10 DC braking time F1.11 Dead time of 0.0~3600.0s FWD/REV Action when running frequency is less than lower F1.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F1.13 F1.14 Name Delay time 0.0~3600.0s for restart F1.12=2) (valid when Restart after 0: Disabled power off F1.15 Setting Description NO. range setting ify 0.0~3600.0 0 ◎ 31. 0~1 0 ○ 32. 0.0~3600.0 0.0s ○ 33. 0~1 0 ○ 34. 1: Enabled Waiting time 0.0~3600.0s of restart Factory mod (valid when F1.14=1) Terminal detection F1.16 selection 0: Disabled 1: Enabled when power on F1.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F2.01 Name Motor rated Description Setting range Motor rated Depend on Motor rated 10.00~F0.0 0.01Hz~F0.03 Motor rated Motor rated current F2.06 Motor stator resistance F2.07 Motor rotor 50.00Hz Depend on 0~36000 0~36000rpm ◎ 39. ◎ 40. ◎ 41. ◎ 42. ◎ 43. ○ 44. ○ 45. ○ 46. ○ 47. model Depend on 0~800 0~800V voltage F2.05 NO. 3 speed F2.04 ify model frequency F2.03 setting 0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting range inductance; F2.10 Current Factory mod setting ify NO. model Depend on 0.1~6553.5 0.01~655.35A without load ○ 48. model F3 Group: Vector Control ASR F3.00 proportional 0~100 20 ○ 49. 0.01~10.00s 0.01~10.00s 0.50s ○ 50. 0.00Hz~F3.05 0.00~F3.05 5.00Hz ○ 51. 0~100 25 ○ 52. 0.01~10.00 1.00s ○ 53. 10.00Hz ○ 54. 0~100 gain Kp1 F3.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name switching Setting Description range frequency) Factory mod NO. setting ify 100% ○ 55. ○ 56. 0 ○ 57. 50.0% ○ 58. 3 point 2 Slip F3.06 50~200 compensatio 50.0%~200.0% n rate of VC G: F3.07 Torque upper limit 0.0~200.0%(the rated 0.0~200.0 current of the inverter) 150.0% P: 120.0% 0: Keypad (corresponds to F3.09) 1:AI1 2:AI2 Torque F3.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name torque Description current of the inverter) Setting range Factory mod NO. setting ify 0~5 0 ○ 59. 0~4 0 ◎ 60. 0 setting 0: Keypad (F0.04) 1: AI1 F3.10 Upper 2: AI2 frequency 3: HDI setting 4: Multi-step source 5:Remote communication (1~4: 100% corresponds to the Max. frequency) F4 Group: V/F Control 0:Linear curve 1:Multidots curve 2: Torque_stepdown curve F4.00 V/F curve selection (1.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F4.01 F4.02 Name Setting Description Torque 0.0%: (auto) boost 0.1%~10.0% Torque 0.0%~50.0% (motor rated Factory mod NO. range setting ify 0.0~10.0 0.0% ○ 61. 0.0~50.0 20.0% ◎ 62. 0.00~F4.05 0.00Hz ○ 63. 0.0~100.0 00.0% ○ 64. 00.00Hz ○ 65. 00.0% ○ 66. 00.00Hz ○ 67. 0.0~100.0 0.0% ○ 68. 0.0~200.0 0.0% ○ 69. boost cut-off frequency) F4.03 V/F 0.00Hz~F4.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting Factory mod NO. range setting ify 0~1 0 ◎ 70. 0~10 0~10 2 ○ 71. 0~10 0~10 0 ○ 72. 0.00~F0.03 30.00 Hz ○ 73. n limit Auto energy F4.10 saving 0: Disabled 1: Enabled selection Low-frequen F4.11 cy threshold of restraining oscillation High-frequen F4.12 cy threshold of restraining oscillation Boundary of F4.13 restraining 0.0~F3.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F5.00 Name HDI selection F5.01 S1 Terminal function F5.02 HDI selection Description 0: High speed pulse input Setting Factory mod NO. range setting ify 0~1 0 ◎ 74. 0~39 1 ◎ 75. 0~39 4 ◎ 76. 0~39 7 ◎ 77. 0~39 0 ◎ 78. 0~39 0 ◎ 79. 1: ON-OFF input 0: Invalid 1: Forward 2: Reverse 3: 3-wire control 4: Jog forward F5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Setting Description Factory mod NO. range setting ify 0~39 0 ◎ 80. 0~39 0 ◎ 81. 0~39 0 ◎ 82. 14: Switch between A and F5.06 S4 Terminal function A+B 15: Switch between B and A+B 16: F5.07 S5 terminal function Multi-step speed reference1 17: Multi-step speed reference 2 18: Multi-step speed reference 3 19: Multi-step speed reference 4 20: Multi-step speed pause F5.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Setting Description Factory mod NO. range setting ify 1~10 5 ○ 83. 0~3 0 ◎ 84. 0.01~50.00 0.50Hz/s ○ 85. 25: Pause PID 26: Pause traverse operation 27: Reset traverse operation 28: Reset counter 29: Reset length 30: ACC/DEC ramp hold 31: Counter input 32: UP/DOWN invalid temporarily 33-39: Reserved F5.09 ON-OFF filter 1~10 times F5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F5.12 Name AI1 lower Description Setting range -10.00~10.0 0.00V~10.00V Factory mod NO. setting ify 0.00V ○ 86. 0.0% ○ 87. 10.00V ○ 88. 100.0% ○ 89. 0 limit AI1 lower F5.13 limit correspondin -100.0~100. -100.0%~100.0% 0 g setting F5.14 -10.00~10.0 AI1 upper limit 0.00V~10.00V 0 AI1 upper F5.15 limit -100.0~100. -100.0%~100.0% 0 correspondin g setting F5.16 AI1 filter time constant F5.17 0.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting Factory mod NO. range setting ify 0.00~10.00 10.00V ○ 93. 100.0% ○ 94. correspondin g setting F5.19 AI2 upper 0.00V~10.00V limit AI2 upper F5.20 limit correspondin -100.0~100. -100.0%~100.0% 0 g setting F5.21 AI2 filter time constant F5.22 0.00s~10.00s 0.00~10.00 0.10s ○ 95. 0.0 kHz ~50.0kHz 0.00~50.00 0.00kHz ○ 96. 0.0% ○ 97. HDI lower limit HDI lower F5.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting range Factory mod NO. setting ify 0.00~10.00 0.10s ○ 100. 0~1 0 ○ 101. 0~20 1 ○ 102. 0~20 4 ○ 103. 0 limit correspondin g setting HDI filter F5.26 time 0.00s~10.00s constant F6 Group: Output Terminals F6.00 HDO selection F6.01 F6.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Setting Description Factory mod NO. range setting ify 0~20 0 ○ 104. 0~10 0 ○ 105. 0~10 0 ○ 106. 7: Zero speed running 8: Preset count value reached 9: Specified count value reached 10: Length reached 11: Simple PLC step completed F6.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name selection Description Setting Factory mod NO. range setting ify 0~10 0 ○ 107. 0.0%~100.0% 0.0~100.0 0.0% ○ 108. 0.00V ~10.00V 0.00~10.00 0.00V ○ 109. 0.0%~100.0% 0.0~100.0 100.0% ○ 110. 0.00V ~10.00V 0.00~10.00 10.00V ○ 111. 3: Output current 4: Output voltage 5: Output power HDO F6.06 6: Output torque function 7: AI1 voltage selection 8: AI2 voltage/current 9: HDI frequency F6.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting Factory mod NO. range setting ify 0.0%~100.0% 0.0~100.0 0.0% ○ 112. 0.00V ~10.00V 0.00~10.00 0.00V ○ 113. 0.0%~100.0% 0.0~100.0 100.0% ○ 114. 0.00V ~10.00V 0.00~10.00 10.00V ○ 115. 0.00%~100.0% 0.00~100.00 0.00% ○ 116. 0.00kHz ○ 117. g output F6.11 AO2 lower limit AO2 lower F6.12 limit correspondin g output F6.13 AO2 upper limit AO2 upper F6.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F6.17 Name AO2 lower Description Setting range 0.000~100.0 0.00%~100.0% 0 limit Factory mod NO. setting ify 100.0% ○ 118. 50.00kHz ○ 119. 0 ○ 120. AO2 lower F6.18 limit 0.000~50.00 0.0 ~ 50.00kHz 0 correspondin g output F7 Group: Human and Machine Interface F7.00 User 0~65535 0~65535 password F7.01 Reserve Reserve Reserve Reserve ○ 121. F7.02 Reserve Reserve Reserve Reserve ◎ 122.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name selection Description Setting Factory mod NO. range setting ify 0~3 0 ○ 125. 0~0XFFFF 0X07FF ○ 1. terminal control 2: Valid when keypad or communication control 3: Always valid 0: Preferential to external keypad 1: Both display, only external Keypad F7.05 display selection key valid. 2: Both display, only local key valid. 3: Both display and key valid.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Setting Description Factory mod range setting ify 0~0XFFFF 0 ○ NO. BIT7: Output power BIT8: Output torque BIT9: PID preset BIT10: PID feedback BIT11: Input terminal status BIT12: Output terminal status BIT13: Torque setting value BIT14: Count value BIT15: Step No. of PLC or multi-step 0~0XFFFF BIT0: AI1 BIT1: AI2 Running F7.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting Factory mod NO. range setting ify 0~0XFFFF 0x00FF ○ 127. 0.1~999.9 100.0% ○ 128. 0.1~999.9 1.0% ○ 129. 0~0XFFFFF BIT0: Reference frequency BIT1: DC bus voltage BIT2: Input terminal status BIT3: Output terminal status Stop status F7.08 display selection BIT4: PID preset BIT5: PID feedback BIT6: AI1 BIT7: AI2 BIT8: HDI frequency BIT9: Step No.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name line speed Setting Description Line speed = range Factory mod setting ify NO. actual mechanical speed * F7.10 Rectify F7.11 module 0~100.0℃ ● 130. 0~100.0℃ ● 131. ● 132. ● 133. ● 134. ● 135. ● 136. temperature IGBT F7.12 module temperature F7.13 Software version F7.14 Inverter 0.4~3000.0kW 0.4~3000.0 rated power F7.15 Inverter module Dpends on 0.0~6000.0A 0.0~6000.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F7.18 Name Setting Description range type 2: IGBT Ph-V fault(SC1) Second 3: IGBT Ph-W fault(SC2) latest 4: Over-current when fault type acceleration(OC1) Factory mod setting ify NO. ● 137. ● 138. 5: Over-current when deceleration(OC2) 6: Over-current constant speed when running (OC3) 7: Over-voltage when acceleration(OV1) F7.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Setting Description range Factory mod setting ify NO.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting range Factory mod setting ify NO. current fault Output F7.21 current at ● 140. ● 141. ● 142. ● 143. ○ 144. current fault DC bus F7.22 voltage at current fault Input terminal F7.23 status at current fault Output F7.24 terminal status at current fault F8 Group: Enhanced Function F8.00 Acceleration time 1 Depend 0.1~3600.0s 0.1~3600.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F8.01 Name Deceleration Description 0.1~3600.0s Setting range 0.1~3600.0 time 1 F8.02 Acceleration Deceleration 0.1~3600.0s 0.1~3600.0 Acceleration 0.1~3600.0s 0.1~3600.0 Deceleration 0.1~3600.0s 0.1~3600.0 0.1~3600.0s 0.1~3600.0 0.00~F0.03(MAX) 0.00~F0.03 0.1~3600.0s 0.1~3600.0 time 3 F8.06 Jog reference Jog F8.07 acceletation ○ 145. Depend ○ 146. Depend ○ 147. Depend ○ 148. ○ 149.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F8.09 Name Skip Description Setting Factory mod NO. range setting ify 0.00~F0.03(MAX) 0.00~F0.03 0.00Hz ○ 153. 0.00~F0.03(MAX) 0.00~F0.03 0.00Hz ○ 154. 0.00~F0.03(MAX) 0.00~F0.03 0.00Hz ○ 155. 0.0~100.0 0.0% ○ 156. 0.0~50.0 0.0% ○ 157. 0.1~3600.0s 0.1~3600.0 5.0s ○ 158. 0.1~3600.0s 0.1~3600.0 5.0s ○ 159. 0~3 0 ○ 160. 0.1~100.0 1.0s ○ 161. Frequency 1 F8.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F8.18 Name Preset count Description Specified range F8.19~6553 F8.19~65535 5 value F8.19 Setting Factory mod NO. setting ify 0 ○ 162. 0~F8.18 0~F8.18 0 ○ 163. 0~65535h 0~65535 65535h ○ 164. 0.00~ F0.03 50.00Hz ○ 165. 0.0~100.0%(FDT LEVEL) 0.0~100.0 5.0% ○ 166. 0.0~100.0%(MAX) 0.0~100.0 0.0% ○ 167. 0.00~10.00Hz 0.00~10.00 0.00Hz ○ 168. 115.0~140.0 130.0% ○ 169. count value F8.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Description Setting Factory mod ify NO. range setting 115.0~140.0 120.0% 0~1 0 ○ 170. 0~1 0 ○ 171. 0~2 0 ◎ 172. 0~5 0 ○ 173. 115.0~140.0%(Standard DC BUS voltage) (220V) threshold F8.26 voltage 0: Auto stop mode Cooling fan 1: Always working control F8.27 Restrain 0: Enabled oscillation 1: Disabled 0: PWM mode 1 F8.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code F9.01 Name Keypad PID Description Setting Factory mod NO. range setting ify 0.0~100.0 0.0% ○ 174. 0~3 0 ○ 175. 0~1 0 ○ 176. 0.00~100.00 0.00~100.00 0.10s ○ 177. 0.01~10.00s 0.01~10.00 0.10s ○ 178. 0.00~10.00s 0.00~10.00 0.00s ○ 179. 0.00~100.00s 0.00~100.00 0.10s ○ 180. 0.0%~100.0% preset 0: AI1 PID F9.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code F9.08 Name Bias limit Description Setting Factory mod NO. range setting ify 0.0~100.0% 0.0~100.0 0.0% ○ 181. 0.0~100.0% 0.0~100.0% 0.0% ○ 182. 0.0~3600.0s 0.0~3600.0 1.0s ○ 183. 0~2 0 ○ 184. 0~1 0 ○ 185. -100.0~100. 0.0% ○ 186. Feedback F9.09 lost detecting value Feedback F9.10 lost detecting time FA Group: Simple PLC and Multi-step Speed Control 0: Stop after one cycle FA.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description 0th Step range Factory mod NO. setting ify 0.0s ○ 187. 0.0% ○ 188. 0.0s ○ 189. 0.0% ○ 190. 0.0s ○ 191. 0.0% ○ 192. 0.0s ○ 193. 0.0% ○ 194. 0 speed 0 FA.03 Setting 0.0~6553.5s(m) 0.0~6553.5 running time FA.04 Multi-step -100.0~100. -100.0~100.0% speed 1 FA.05 1st Step 0 0.0~6553.5s(m) 0.0~6553.5 running time FA.06 Multi-step -100.0~100. -100.0~100.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code FA.11 Name 4th Step Description 0.0~6553.5s(m) Setting Factory mod NO. range setting ify 0.0~6553.5 0.0s ○ 195. 0.0% ○ 196. 0.0s ○ 197. 0.0% ○ 198. 0.0s ○ 199. 0.0% ○ 200. 0.0s ○ 201. 0.0% ○ 202. 0.0s ○ 203. running time FA.12 Multi-step -100.0~100. -100.0~100.0% 0 speed 5 FA.13 5th Step 0.0~6553.5s(m) 0.0~6553.5 running time FA.14 Multi-step -100.0~100. -100.0~100.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code FA.20 Name Multi-step Description 9th Step range -100.0~100. -100.0~100.0% Factory mod NO. setting ify 0.0% ○ 204. 0.0s ○ 205. 0.0% ○ 206. 0.0s ○ 207. 0.0% ○ 208. 0.0s ○ 209. 0.0% ○ 210. 0.0s ○ 211. 0.0% ○ 212. 0 speed 9 FA.21 Setting 0.0~6553.5s(m) 0.0~6553.5 running time FA.22 Multi-step -100.0~100. -100.0~100.0% 0 speed 10 FA.23 10 th Step 0.0~6553.5s(m) 0.0~6553.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code FA.29 Name 13 th Step Description 0.0~6553.5s(m) Setting Factory mod NO. range setting ify 0.0~6553.5 0.0s ○ 213. 0.0% ○ 214. 0.0s ○ 215. 0.0% ○ 216. running time FA.30 Multi-step -100.0~100. -100.0~100.0% 0 speed 14 FA.31 14 th Step 0.0~6553.5s(m) 0.0~6553.5 running time FA.32 Multi-step -100.0~100. -100.0~100.0% 0 speed 15 FA.33 15th Step 0.0~6553.5s(m) 0.0~6553.5 0.0s ○ 217.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Description restart 1: Continue from paused selection FA.37 Setting Name NO. range setting ify 0~1 0 ◎ 221. 0~1 1 ○ 222. 0~1 1 ○ 223. 0~2 2 ◎ 224. 20.0~120.0 100.0% ○ 225. step 0: Second Time unit Factory mod 1: Minute Fb Group: Protection Function Input Fb.00 phase-failure protection 0: Disable 1: Enable Output Fb.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name overload Setting Description Factory mod NO. range setting ify 70.0~110.0 80.0% ○ 226. 0.00~F0.03 0.00Hz/s ○ 227. 0~1 1 ○ 228. 110~150% 110~150 120% ○ 229. 50~200% 50~200 ○ 230. ○ 231. current of the motor) protection current Fb.04 Threshold of 70.0.0~110.0% trip-free Decrease Fb.05 rate of trip-free (standard bus voltage) 0.00~F0.03 (the Max. frequency) Over-voltage Fb.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Setting Description Factory mod NO. range setting ify 0~1 0 ○ 232. 0~4 1 ○ 233. decrease rate when current limiting Auto current 0: Enabled Fb.10 limiting selection 1: Disabled when constant speed 0:No detection 1 : Valid detection of overtorque during running, then continue running 2 : Valid Selection of Fb.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Setting Description range Factory mod setting ify NO. overtorque during constant speed running, then waring and stop. Detection 10.0%~200.0%(relative to G:150.0% Fb.12 level of the rated current of the 1.0~200.0 ○ 234. ○ 235. P:120.0% overtorque motor) Detection Fb.13 time of 0.1~60.0s 0.0~60.0 0.1s overtorque Fb.14 Reserved ● 236. Fb.15 Reserved ● 237.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description Setting Factory mod range setting ify 0~5 1 ○ NO. 5: 38400BPS 0: RTU, 1 start bit, 8 data bits, no parity check, 1 stop bit. 1: RTU, 1 start bit, 8 data bits, even parity check, 1 stop bit. 2: RTU, 1 start bit, 8 data bits, odd parity check, 1 stop bit. FC.02 Data format 3: RTU, 1 start bit, 8 data bits, no parity check, 2 stop bits.
JAROL Assumes the promotion of energy-saving technology as its own task! Function code Name Setting Description Factory mod NO. range setting ify 0~200 5ms ○ 241. 0.0~100.0 0.0s ○ 242. 0~3 1 ○ 243. 00~11 00 ○ 244. Communicati FC.03 on 0~200ms delay time Communicati FC.04 on timeout 0.0: Disabled 0.1~100.0s delay 0: Alarm and coast to stop 1: No alarm and continue to run Communicati FC.05 on error action 2: No according alarm to but stop F1.06 (if F0.
JiaXing Jarol Scientific Instrument Co.,Ltd-JR6000 series products Function code Name Description when power off 1: Reference saved when power off FD Group: Supplementary Function FE Group: Factory Setting 182 Setting range Factory mod setting ify NO.