Installation Guide

(Ceiling Opening is to be 6 7/8"Dia.)
INSTALLATION IN WOOD JOISTS
This Instruction sheet is also intended to be used as a Paint Shield.
Follow this Instruction Sheet Carefully. Be sure Electricity is OFF before starting Installation.
1.- Slip Bar Hangers (1) through slots in Plaster Frame (2). Hold Frame in desired position between
Joists (3) and drive Bar Hanger Tabs (4) into Joists. Use a minimum 1" lg. steel Nail or Screw (26)
through holes in Bar Hanger ends for additional support. Tighten bar hanger Locking Screws (5) in
ends of Plaster Frame to prevent lateral movement of Plaster Frame. (See Fig. 1 and 2)
2.- Remove Cover Plate (9) from Junction Box (10). Slip Type NM Cable (Romex) (11) through desired
hole in Junction Box (10) above Retaining Plate (13). Cable (11) is secured by Retaining Plate (13).
(See Fig. 3)
3.- If other than Type NM Cable (Romex) is to be used, remove one Large Knockout (15) at desired
location on top or sides of Junction Box (10). Bring appropriate Electrical Supply Cable into Junction
Box and secure in place with proper UL listed Connector (NOT FURNISHED).
4.- Connect Fixture Wires (27) to Supply Wires (16) as shown in Wiring Diagram. Use UL listed
Wirenuts (NOT FURNISHED).
5.- After ceiling is finished, lower Housing (6) until flush with Ceiling.
6.- To gain access to Junction Box (10), after Ceiling is finished, remove three Screws (24) that hold
Housing (6) in place. Lower the Housing. Remove Screw (21) and Access Door (22) located inside
Fixture. Junction Box Cover Plate (9) can now be removed for service.
7.- Plaster Frame (2) and Gasket (25) must be in contact with Ceiling (23).
8.- If joists are spaced greater than 16 inches on center, 2x4 (4 inch dimension vertical) or greater
lumber shall be used to span between joists at the plane of the ceiling to create a 16 inch on center
space to mount the fixture as shown in Fig. 4.
9.- If steel furring channels are used in the ceiling, Plaster Frame (2) must be lowered until Gasket (25)
contacts Ceiling (23) as shown in Fig. 5.
When installed according to the instructions provided and as specified in Volume 1 of the UL Fire
Resistance Directory, Progress P821-FB & P821-FBT luminaires may be used in fire resistant
Floor-Ceiling and Roof-Ceiling designs. See File #R19217 under Fire Classified Directory CDHW.
SPEC.NO.
Assembly & Installation Instructions
Read instructions carefully and turn electricity off at main
circuit breaker panel before beginning installation.
CAUTION:
PAGE of
01-15-03023567
P821-FB & P821-FBT
1 6
***************************************************************************************************************************************************************
***************************************************************************************************************************************************************
WARNING: - If any Special Control Devices are used with this fixture, follow the instructions carefully
to assure full compliance with N.E.C. requirements. If there are any questions, contact a Qualified
Electrical Contractor.
W
ARNING: Use only those Trims, Lamps and maximum Wattage's proper for this Fixture, as
indicated on the Label within the Fixture Housing.
W
ARNING: The National Electrical Code, Article 110-3 (b), states that "Listed or Labeled equipment
shall be used or installed in accordance with any Instructions included in the listing or labeling".
Use only with Progress UL listed Trims. Use of other Trims not listed in this Fixture, including
those that are UL classified, is a violation of N.E.C. 110-3 (b) and voids all warranties.
Upon completion of installation, crumple this sheet up and insert it up into
the housing to protect the socket and labels from being spray painted.
*** This is a Non-IC Housing. Insulation must be kept 3" away from fixture to prevent lights from blinking. ***

Summary of content (6 pages)