Dispenser-Specific Configuration Settings
Some dispenser brands have specific configurations available. Follow the steps below to change the
configuration for each fueling position.
1. At the top level of Diagnostics, select D to enter Section Diagnostics.
2. Select the Dispenser Interface Section to be configured (1 or 2).
3. Select P for Pump Diagnostics.
4. If the dispenser brand has specific settings, select C to Configure Pump. If the dispenser does
not have settings, this option will not be available.
5. Settings are for an individual fueling position, so the configuration must be changed for all
dispensers that the Omega JR will be controlling. The only exception is for the Gilbarco
Channel Speed setting which affects the entire channel.
Table: Dispenser-Specific Configurations
Brand Available Settings
Deer Number of Displays (1 or 2)
Volume Decimal Digits (2 or 3)
Preset Digits (4 or 6)
PPU Decimal Places (0, 1, 2, or 3)
Gilbarco Channel Speed (Modular or Legacy)
Hose Test (yes or no)
Special Function Commands (yes or no)
Kraus Pump Head Type (Kraus or MTI)
PPU Decimal Point (0, 1, 2, or 3)
Volume Decimal Point (0, 1, 2, or 3)
Dollar Decimal Point (0, 1, 2, or 3)
Nuovo Pignone Volume Decimal Places (2 or 3)
Tokheim Unit of Measure (Litres or Gallons)
Volume Decimal Point (2 or 3)
Wayne BCD (enabled or disabled)
Number of Displays (1 or 2)
Manual Decimal Point Configuration (list of available options)
Default Decimal Point Configuration
MOP Switches (yes or no)
Unit of Measure (Litres or Gallons)
Bennett, Dong Hwa, Mechanical, Schlumberger, Tatsuno, and PMC do not have
configuration settings.
Version 1.0 Page 9 February 2013