Troubleshooting
The ProNauticP includes advanced fault indication. Faults, if indicated, may require service
from ProMariner. For inquiries and service information Please call our Customer Care
Department line at 1-800-824-0524 from 8:30 am to 5 pm (Eastern Standard Time) for any
warranty, service or installation assistance you may need. Thank You
! THERE ARE NO USER SERVICEABLE PARTS INSIDE THE PRONAUTICP. DO NOT
ATTEMPT TO DISSASEMBLE THE UNIT. EVIDENCE OF DISSASEMBLY WILL VOID
MANUFACTURERS WARRANTY.
The first step to any problem is resetting the ProNauticP unit by turning off the AC breaker
providing power, waiting at least 10 seconds and turning it back on again.
Review the Operations section for the meaning of the fault indicator and suggestions on
how to clear the fault.
Charger Fault (Service) Conditions
LED Label LED Color Fault
Reverse Polarity Red Indicates a reverse polarity situation
Check DC Connections, ensure positive + (RED) and negative - (BLACK and/or YELLOW)
connections are attached accordingly
DC Volts Low Amber DC system voltage is less than 11.0 VDC
Bring system voltage over 11.0 VDC, check battery(s) condition and replace as necessary.
DC Volts High Red Indicates a high DC voltage from an outside source
such as a failed alternator
Using a multi-meter check alternator(s) output, generally over 15VDC. Determine if fault exists
in regulator or alternator, solar panel, wind generator etc. Replace as needed.
Charger High Temp Amber Charger has shut down due to high temperature
Generally this indicates that the unit has been installed in an area with a very high ambient temperature.
This unit is designed for use in an engine room, if installed in an engine compartment; ensure that there
is proper ventilation in the space for the charger and other temperature sensitive components. If the
installation area temperature is 45° C (113° F) or more, move charger or add ventilation to lower ambient
temperature. The recommended maximum ambient temperature for installation is 45° C. (113° F)
Check Fan Red Fan failure
Ensure that the cooling fan can move freely and that no debris is blocking the fan movement.
Persistent fan problems require service from ProMariner.
Fault Red Indicates a fault
Please contact ProMariner for service options.
Auto Temp Control Red flashing High temp causes unit shutdown
See charger high temp above
Note: Installation is permitted in an environment of 45
°
C (113
°
F) and may result in output
of unit decreasing to protect the internal components and the performance of the unit.
Programming
4. Press the “Setup/Enter” button to confirm selection.
NOTE: If no action is taken after 15 seconds, the unit reverts to 100% power.
FACTORY RESET
To return the unit to original factory settings (Sealed 2)
1. Follow steps 1 and 2 in the Selecting Battery Type section
2. Use the
and keys until no battery type or equalization LED’s are illuminated.
3. The Voltage and Amperage displays will show “FAC” “DEF” for factory default.
4. Press the “Setup/Enter” button to confirm selection, the charger will re-boot.
PROGRAMMING USING THE OPTIONAL REMOTE
1. Pressing SETUP/ENTER displays “SCROLLING”
2. Using the
and (directional) keys scroll through the below menu items,
3. Pressing SETUP/ENTER will activate each mode,
4. Using the directional keys again will display additional options to be selected,
press SETUP/ENTER when done
19
Remote Panel “Scrolling” Menu Options
1. Charger Name Displays charger model
2. Charger Status Displays Charging/Conditioning/Ready
3. Battery Type Selection Scroll through available types,
4. Time to Absorption Displays time left in Absorption mode.
5. Run time Displays units total run-time
6. Power Level Displays current power level, allows selection.
7. Battery Temperature Displays battery temperature
8. Charger Temperature Displays charger temperature
9. Transformer Temperature Displays transformer (AC side) temperature
10. Faults Displays “No Faults Detected” OR allows scrolling through faults,
if present, once SETUP/ENTER is pressed, see the Troubleshooting section.
11. Company Information Displays Professional Mariner information
12. Total Run Time Displays log of total run time
13. Software revision Displays the current software version
Remote Shortcuts
Press and hold for 10 seconds to force into Ready mode
Press and hold for 15 seconds for direct access to power level mode
Press and hold for 5 seconds to initiate Self Test
Press and hold for 3 seconds, restores Factory Default
NOTES:
*All remote modes/functions are identical to those described by using the on-charger controls.
*10 seconds of inactivity will cause the remote to revert to the previous setting.
Setup
Enter
Alarm
Setup
Enter