Chapter 4: Management with WebPAM PROe
81
Making UPS Settings
These settings control how the VTrak subsystem detects the UPS unit and
responds to data reported by the UPS unit.
To make UPS settings:
1. Click the Device tab.
2. Click the UPS icon.
3. Click the UPS Settings button.
4. Perform the following actions as required:
Verify the Current UPS Communication method. See Note 1:
SNMP – Network connection.
Serial – Serial connection.
Unknown – No connection.
Choose a Detection Setting from the dropdown menu:
Automatic – Default. If a UPS is detected when the subsystem
boots, the setting changes to Enable.
Enable – Monitors UPS. Settings changes, reports warnings, and
logs events.
Disable – Monitors UPS only.
Type values into the Threshold fields. See Note 2:
Running Time Remaining Threshold – Actual time below this
value resets adaptive writeback cache to writethrough.
Warning Temperature Threshold – Actual temperature above this
value triggers a warning and logs an event.
Loading Ratio Threshold – Actual loading ratio (percentage)
above this threshold triggers a warning and logs an event. See
Note 3.
For UPS units with network cards, type the IP addresses or DNS names
in fields UPS 1 and UPS 2. See Note 4.
5. Press Ctrl-A to save your settings.
Note 1: VTrak supports multiple UPS units using network or serial
connections, but not a combination of both methods.
Note 2: Detection Setting must be set to Auto. If a UPS is detected, the
setting changes to Enable.
Note 3: The maximum recommended Loading Ratio varies among models of
UPS units. The general range is 60% to 80%.
Note 4: To specify UPS units by DNS names, ask your IT administrator to
add the DNS names to the DNS server, before you make UPS settings.