Temperature Thresholds
Temperature thresholds are the temperature levels the Controller will report as a
Warning or Critical. For most applications, the factory default settings are
recommended.
To change temperature thresholds:
1. Highlight the Enclosure Temperature Warning threshold and press the
backspace key to erase the current value.
2. Type a new interval value in degrees C.
Note the acceptable range of temperature values in the brackets. The default
values are as follows:
Enclosure Warning, 45°C
Enclosure Critical, 51°C
Controller Warning, 63°C
Controller Critical, 68°C
3. Do the same action to set the other thresholds.
4. Press Ctrl-A to save your settings.
Batteries
This feature enables you monitor and recondition the subsystem battery or
batteries.
1. From the Main Menu, highlight Subsystem Management and press Enter.
2. Highlight Enclosure Management and press Enter.
3. Highlight Batteries and press Enter.
4. Highlight the battery you want to monitor and press Enter.
5. Battery condition is expressed in the following items:
Temperature Threshold Discharge – If battery exceeds this value while
charging, replace the battery
Battery Temperature – Should stay below charge and discharge
thresholds
Battery Voltage – Approximately 3900 mV is normal
Battery Status – “FullyCharged” is normal. If it is says “Malfunction”,
replace the battery
Remaining Capacity – When status is “FullyCharged”, capacity should
be at least 90%. If less, replace the battery
Temperature Threshold Charge – If battery exceeds this value while
charging, replace the battery