VTRAK M-CLASS Product Manual

VTrak M-Class Product Manual
260
There is no spare drive at this moment. Even if physical drive 5 is of adequate
capacity, it has not been designated as a spare, therefore the controller cannot
use it as a spare.
Automatic Transition
At this juncture, you would replace the failed drive in slot 3 with a new one of the
same or greater capacity.
When the VTrak controller detects the new drive in slot 3, it will:
Automatically transition the data on drive 6 to drive 3
Return drive 6 to spare status
When the Automatic Transition is finished, physical drives 1, 2, 3, and 4 belong to
the disk array and physical drive 6 is a revertible spare drive. The original
configuration is restored.
Manual Transition
If you wanted to use the drive in slot 5 as a member of the disk array, rather than
the drive in slot 3, you would run the Transition function manually. See page 140
(WebPAM PROe) or page 187 (CLU).
When the Manual Transition is finished, physical drives 1, 2, 4, and 5 belong to
the disk array and physical drive 6 is a revertible spare drive.
At this point, you would replace the drive in slot 3. The new drive in slot 3 will be
unconfigured until you assign it to a disk array or as a spare.