User manual
Reference  MVI56-HART ♦ ControlLogix Platform 
User Manual  HART Multi-drop Master Communication Module 
Page 122 of 171  ProSoft Technology, Inc. 
  October 13, 2011 
COMMAND 06 - Write Polling Address 
Description 
This command sets the polling address of a HART device. Extreme care should be taken 
when you use this command because you can loose the communication with the device. 
Write Parameters 
Word  High Byte  Low Byte 
0  Polling Address  Polling Address 
Floating Point Data Returned 
NONE 
Integer Data Returned 
Word  High Byte  Low Byte 
0  STATUS WORD 
1  Polling Address  0 










