User manual
Reference  MVI56-HART ♦ ControlLogix Platform 
User Manual  HART Multi-drop Master Communication Module 
Page 128 of 171  ProSoft Technology, Inc. 
  October 13, 2011 
COMMAND 17 - Write Message 
Description 
This command writes an ASCII message contained in the HART Device and that can be 
read with command 12. 
Write Parameters 
Word  High Byte  Low Byte 
0  Packed ASCII Message Byte 0  Packed ASCII Message Byte 1 
1  Packed ASCII Message Byte 2  Packed ASCII Message Byte 3 
. 
. 
. 
. 
. 
. 
11  Packed ASCII Message Byte 22  Packed ASCII Message Byte 23 
Floating Point Data Returned 
NONE 
Integer Data Returned 
Word  High Byte  Low Byte 
0  STATUS WORD 