MVI56-HART ♦ ControlLogix Platform  Reference 
HART Multi-drop Master Communication Module   User Manual 
ProSoft Technology, Inc.  Page 131 of 171 
October 13, 2011 
5.10  HART Common Practice Commands 
COMMAND 33 - Read Transmitter Variables 
Description 
This command gets four user selected dynamic Variables. 
Write Parameters 
Word  High Byte  Low Byte 
0  Transmitter Variable Code For Slot 0  Transmitter Variable Code For Slot 1 
1  Transmitter Variable Code For Slot 2  Transmitter Variable Code For Slot 3 
Floating Point Data Returned 
Word  High Byte  Low Byte 
0  Variable for Slot 0 
1 
2  Variable for Slot 0 
3 
4  Variable for Slot 2 
5 
6  Variable for Slot 3 
7 
Integer Data Returned 
Word  High Byte  Low Byte 
0  STATUS WORD 
1  Transmitter Variable Code For Slot 0  Units Code for Slot 0 Variable 
2  Transmitter Variable Code For Slot 1  Units Code for Slot 1 Variable 
3  Transmitter Variable Code For Slot 2  Units Code for Slot 2 Variable 
4  Transmitter Variable Code For Slot 3  Units Code for Slot 3 Variable 