User manual
MVI56-HART ♦ ControlLogix Platform  Reference 
HART Multi-drop Master Communication Module   User Manual 
ProSoft Technology, Inc.  Page 133 of 171 
October 13, 2011 
COMMAND 35 - Write Range Values 
Description 
This command writes the Upper and Lower range of the Primary Variable 
Write Parameters 
Word  High Byte  Low Byte 
0  Range Units Code  Floating Point Upper Range Value (Byte 0) 
1  Floating Point Upper Range Value (Byte 1)  Floating Point Upper Range Value (Byte 2) 
2  Floating Point Upper Range Value (Byte 3)  Floating Point Lower Range Value (Byte 0) 
3  Floating Point Lower Range Value (Byte 1)  Floating Point Lower Range Value (Byte 2) 
4  Floating Point Lower Range Value (Byte 3)  Floating Point Lower Range Value (Byte 3) 
Floating Point Data Returned 
Word  High Byte  Low Byte 
0  Upper Range Value 
1 
2  Lower Range Value 
3 
Integer Data Returned 
Word  High Byte  Low Byte 
0  STATUS WORD 
1  Range Units Code  0 










