User manual
Reference  MVI56-HART ♦ ControlLogix Platform 
User Manual  HART Multi-drop Master Communication Module 
Page 142 of 171  ProSoft Technology, Inc. 
  October 13, 2011 
COMMAND 44 - Write PV Units 
Description 
This command changes the setting of the Primary Variable units. 
Write Parameters 
Word  High Byte  Low Byte 
0  Primary Variable Units Code  Primary Variable Units Code 
Floating Point Data Returned 
NONE 
Integer Data Returned 
Word  High Byte  Low Byte 
0  STATUS WORD 
1  Primary Variable Units Code  0 