MVI56-HART ♦ ControlLogix Platform  Configuring the MVI56-HART Module 
HART Multi-drop Master Communication Module   User Manual 
ProSoft Technology, Inc.  Page 37 of 171 
October 13, 2011 
Auto-Poll DB Address 
0 to 3700 
This parameter sets the starting address for the data obtained by the auto-poll feature. 
Each device on a channel requires 50 words in the database. The data area selected 
must not overlap any portion of the database used by other channels or the module. 
Auto-Poll Swap Float 
0 to 3 
This parameter swaps the floating-point data values received by the auto-poll feature. 
Swap Code  Description 
0  None - No Change is made in the byte ordering (1234 = 1234) 
1  Words - The words are swapped (1234=3412) 
2  Words & Bytes - The words are swapped then the bytes in each word are 
swapped (1234=4321) 
3  Bytes - The bytes in each word are swapped (1234=2143) 
Depending on the host processor using the data, the proper swap code must be utilized 
to present the data in the correct format. 
Max Device Count 
1 to 15 
This parameter sets the maximum number of slave devices to be utilized for the auto-poll 
feature. In point-to-point mode, the parameter should be set to a value of 1. In multi-drop 
mode, the parameter should be set from 1 to 15 to represent the number of slave devices 
attached to the channel. 