User manual
Configuring the MVI56-HART Module  MVI56-HART ♦ ControlLogix Platform 
User Manual  HART Multi-drop Master Communication Module 
Page 48 of 171  ProSoft Technology, Inc. 
  October 13, 2011 
Index  Parameter  Value  Observation 
12  Enable 
Address 
-1  This command does not use this feature 
13  DB Done 
Address 
-1  This command does not use this feature 
14  DB Write 
Address 
800  The floating point value located at byte-address 800 
(word-address 400) will be used as the damping 
value to be written to the HART device 
15  DB Swap Code
3  The bytes in each returned integer data will be 
swapped 
16  Byte Count  4  The command will write 4 bytes (2 words) to the 
HART device, since the damping value uses floating 
point format (2 words) 
17  Fixed Data    This command does not use this feature 
The user would have to verify that addresses 300 and 320 are located inside the Read 
Data area (read from the MVI database to the PLC processor). Address 400 would have 
to be located inside the Write Data area (written from the PLC processor to the MVI 
database). 










