Viewing Block Transfer Statistics 
Press [B] from the Main menu to view the Block Transfer Statistics screen. 
Use this command to display the configuration and statistics of the backplane data 
transfer operations between the module and the processor. The information on this 
screen can help determine if there are communication problems between the processor 
and the module. 
Tip: To determine the number of blocks transferred each second, mark the 
numbers displayed at a specific time. Then some seconds later activate the 
command again. Subtract the previous numbers from the current numbers and 
divide by the quantity of seconds passed between the two readings. 
Viewing Module Configuration 
Press [C] to view the Module Configuration screen. 
Use this command to display the current configuration and statistics for the module. 
Opening the Database View Menu 
Press [D] to open the Database View menu. 
Use this menu command to view the current contents of the module’s database. For 
more information about this submenu, see Database View Menu. 
Opening the HART Master Menu 
Press [H] to open the HART Master Menu. This menu allows you to view information 
about the protocol driver. 
Transferring the Configuration File from the PC to the Module 
On the Diagnostics Menu this is referred to as Receive Module Configuration. 
Press [R] to receive (download) the configuration file from your PC to the module and 
store the file on the module’s Compact Flash Card (Personality Module) or Flash RAM.  
Press [Y] to confirm the file transfer, and then follow the instructions on the terminal 
screen to complete the file transfer process. 
After the file has been successfully downloaded, the module will restart the program and 
load the new configuration information. Review the new configuration using menu 
commands [6] and [0] to verify that the module is configured correctly. 