4.2.2  Troubleshooting 
Use the following troubleshooting steps if you encounter problems when the module is 
powered up. If these steps do not resolve your problem, please contact ProSoft 
Technology Technical Support. 
Processor Errors 
Problem description  Steps to take 
Processor fault  Verify that the module is plugged into the slot that has been configured 
for the module in the I/O Configuration of RSLogix. 
Verify that the slot location in the rack has been configured correctly in 
the ladder logic. 
Processor I/O LED 
flashes 
This indicates a problem with backplane communications. A problem 
could exist between the processor and any installed I/O module, not just 
the MVI56-HART. Verify that all modules in the rack are correctly 
configured in the ladder logic. 
Module Errors 
Problem description  Steps to take 
BP ACT LED (not 
present on MVI56E 
modules) remains OFF 
or blinks slowly 
MVI56E modules with 
scrolling LED display: 
<Backplane Status> 
condition reads ERR 
This indicates that backplane transfer operations are failing. Connect to 
the module’s Configuration/Debug port to check this. 
To establish backplane communications, verify the following items: 
  The processor is in RUN or REM RUN mode. 
  The backplane driver is loaded in the module. 
  The module is configured for read and write data block transfer. 
  The ladder logic handles all read and write block situations. 
  The module is properly configured in the processor I/O configuration 
and ladder logic. 
OK LED remains RED  The program has halted or a critical error has occurred. Connect to the 
Configuration/Debug port to see if the module is running. If the program 
has halted, turn off power to the rack, remove the card from the rack and 
re-insert it, and then restore power to the rack. 