User manual
Reference  MVI56-HART ♦ ControlLogix Platform 
User Manual  HART Multi-drop Master Communication Module 
Page 88 of 171  ProSoft Technology, Inc. 
  October 13, 2011 
Word Offset in Block  Data Field(s)  Description 
4  Start Index of 
First 
Command 
This field contains the index in the command list for the 
first value in the file. This field will have a value of 0 to 
MaxCommands-1. 
5 to 104  Command 
List Errors 
Each word of this area contains the last error value 
recorded for the command. The command index of the 
first value (offset 4) is specified in word 3 of the request 
block. The number of valid command errors in the block is 
set in word 3 of the block. Refer to the command error list 
to interpret the error codes reported. 
105 to 248  Spare  Not Used 
249  Block ID  This field contains the value of 9950 identifying the block 
type to the PLC. 
For further information concerning the status blocks (0 and -1) please refer to Status 
Data. 
Block 9998: Warm Boot 
Block 9998 performs a warm-boot operation on the module. The following table describes 
the format of the block constructed by the processor. 
Offset  Description  Length 
0  9998  1 
1 to 247  Spare  247 
Block 9999: Cold Boot 
Block 9999 performs a cold-boot operation on the module. The following table describes 
the format of the block constructed by the processor. 
Offset  Description  Length 
0  9999  1 
1 to 247  Spare  247 