For response messages from HART devices, it is possible to configure where the 
Floating Point Data and Integer Data will be placed in the module’s internal database, but 
this is only possible for the Universal and Common Practice commands. In the case of 
Device Specific commands, all the Read Data is placed in the Integer data section. See 
HART Command Support for a listing of supported HART commands. 
Burst Mode 
If a slave on a network will be placed in burst mode, its data can be placed in the 
module's database. For the command to be burst by slave device, enter a command in 
the user command list with the appropriate HART command number. Set the type field to 
0 to disable the command. The parameters in the command will be used to store the data 
received from the bursting slave. There can only be one slave bursting on the network at 
any one time. This mode can be used for faster update of data from a slave. 
Auto-Polling 
This feature is enabled by setting the AUTO-POLL CODE (in the configuration file) to a 
value of P (point-to-point). If the value N is entered for the parameter, the auto-poll 
feature is disabled. When the feature is disabled, the channel will only execute the 
commands enabled in the user command list. When the auto-polling mode is enabled, 
the module will automatically acquire data from the HART instruments attached to a 
channel without the use of user commands. If user commands are present and enabled 
when the feature is enabled, they will also be executed independent of auto-polling. 
With the auto-poll feature enabled, the module automatically generates the following 
HART commands and stores the data in the module's database at the user-specified 
location: 
CMD  Description 
0  Read Unique Identifier 
3  Read Current and Four Dynamic Variables 
13  Read Tag, Descriptor and Date 
14  Read PV Sensor Information 
15  Read Output Information 
If the unit is set for point-to-point mode, the module will automatically gather the 
information for the device with the polling address (short address) of zero and place the 
data into the database. Each device requires a 50-word database area with the format 
shown in the following table. 