If the module is configured for multi-drop auto-polling (Auto-Poll Code = M), the following 
diagram applies: 
In multi-drop mode, the channel will poll for instruments 1 to the value set in the MAX 
DEVICE COUNT parameter. For each device found, it will continuously poll for data using 
command 3. After a certain number of iterations, the HART Driver will ready the 
configuration data for the next device (if there is one). Each time configuration information 
is acquired, it will be for a different slave device if more than 1 slave is recognized by the 
channel. Less frequently, the channel will poll for devices not found in the original search 
of the network using HART command 0. If communications is lost with all devices, the 
module will try to establish communications with the devices using command 0. If user 
commands are present and enabled, they will be executed after the data polling of the 
devices. 
Multi-drop Mode Example: 
The intent is to show when using Multi-drop mode how the Auto-Poll DB Address and 
Max Device Count parameters should be used. 
If the configuration file sets the following parameters: 
Parameter  Value  Config File Section 
DB Address Status  3660   
[HART PORT 0] 
Auto-Poll DB Address  400 
Max Device Count  15 