User manual
1560-PDP 
PROFIBUS – SCANport Adapter 
  6   
Dip Switches – SW1 
8  7  6  5  4  3  2  1 
Name 
Description 
  X  X  X  X  X  X  X  Node 
Address 
Selects the Profibus Node address 
for this adapter. Binary weighting on 
dip switches as follows: 
Bit  Value 
0  1 
1  2 
2  4 
3  8 
4  16 
5  32 
6  64 
Example: 
6  5  4  3  2  1  0  Addr 
0  0  0  0  0  0  1  1 
0  0  0  0  0  1  0  2 
0  0  0  0  0  1  1  3 
-  -  -  -  -  -  -  - 
1  1  1  1  1  1  1  127 
X                Loss of 
Comm 
Failure 
Enable 
The action that the adapter will take 
upon detecting loss of control from a 
Siemens host. This action will not be 
enabled until an initial Output 
Command has been received from 
the host, and the Timeout has 
expired (See SW2 table below): 
0 = Disable Failure 
1 = Enable Failure 
Dip Switches – SW2 
8  7  6  5  4  3  2  1 
Name 
Description 
              X  Byte Swap 
(Default off) 
Position is a function of the 
Profibus host device  
1 for Siemens S5 
0 for all others 
        X  X  X    Loss of Comm 
Timeout Multiplier 
The adapter has a default 
timeout of 120ms. To adjust this 
value, use the following positions: 
    Timeout 
432  Value 
000  120ms 
001  120ms 
010  240ms 
011  360ms 
100  480ms 
101  600ms 
110  720ms 
111  840ms 










