User manual
1560-PDP 
PROFIBUS – SCANport Adapter 
  23   
E.4 : Adapter Output Image (Write to 1560-PDP) 
Word
Name
Description
0
Diagnostics Control 
Byte
When writing to a parameter 
enter a value of (0x10h) This 
will oneshot the parameter 
value
1 Logic Control Word This word should be verified in 
the A-B user manual for the 
particular device being 
controlled.
2 Reference Control This word should be verified in 
the A-B user manual for the 
particular device being 
controlled.
3 Datalink - A1 Adapter I/O (*Number of 
Datalinks set by DIP switch)
4 Datalink - A2 Adapter I/O (*Number of 
Datalinks set by DIP switch)
5 Datalink - B1 Adapter I/O (*Number of 
Datalinks set by DIP switch)
6 Datalink - B2 Adapter I/O (*Number of 
Datalinks set by DIP switch)
7 Datalink - C1 Adapter I/O (*Number of 
Datalinks set by DIP switch)
8 Datalink - C2 Adapter I/O (*Number of 
Datalinks set by DIP switch)
9 Datalink - D1 Adapter I/O (*Number of 
Datalinks set by DIP switch)
10 Datalink - D2 Adapter I/O (*Number of 
Datalinks set by DIP switch)
11
Parameter Number 
Write
Enter the value for the 
parameter you wish to write 
to(Parameter 112 = 112)
12 Parameter Value Enter the value to set the 
parameter to
Writing A Parameter 
1.  Enter the parameter 
number into word 11 
2.  Enter the parameter value 
into word 12 
3.  Enter value 0x10h in word 
0(This will oneshot the 
value to the parameter) 
4.  Clear word 0 